12V Battery Runtime Calculator
A 100 Ah, 12 V lead-acid battery runs a 100 W load through an inverter for about 4 h 3 min, using only the 50% of its capacity that is safe to use. Runtime in hours equals Ah × volts × usable depth of discharge ÷ (load watts ÷ inverter efficiency + the inverter's idle draw); for a DC load set the efficiency to one.
How this result was calculated
100 Ah × 12 V × 50% usable = 600 Wh in the battery. The battery gives 100 W ÷ 85% inverter efficiency + 30 W the inverter draws itself = 147.6 W. 600 Wh ÷ 147.6 W = 4.06 hours, about 4 h 3 min. Battery current: 147.6 W ÷ 12 V = 12.3 A, 0.12 times the battery's Ah (its C-rate), rising to 14.1 A as the battery nears its low-battery cut-off; the cables and fuse must carry that.
Key facts
- Runtime of a 12 V battery in hours = Ah × 12 V × usable depth of discharge ÷ (load watts ÷ inverter efficiency + the inverter's idle draw).
- A 100 Ah, 12 V lead-acid battery stores about 600 Wh of usable energy, which through an inverter runs a 100 W load for about 4 h 3 min or a 1,000 W load for about 29 min.
- Lead-acid, AGM and gel batteries should be used to about 50% of their rating; lithium (LiFePO4) batteries to about 90%, so a lithium battery of the same Ah runs almost twice as long.
- An inverter running at about 85% efficiency turns the rest of the battery energy into heat; the inverter also draws about 30 W itself while it is on. A DC load wired straight to the battery has neither loss.
Formula
t = (Ah × V × DoD) ÷ (P ÷ η + P_idle)
- t = runtime in hours
- Ah = battery capacity in amp hours
- V = battery voltage (nominal)
- DoD = usable depth of discharge
- η = inverter efficiency (1 for a DC load)
- P_idle = the inverter's own draw with no load (from its label; none for a DC load)
- P = load in watts
How long will a 12 V battery run a 100 W load?
A 100 Ah, 12 V lead-acid battery runs a 100 W AC load for about 4 h 3 min through an inverter. The same load wired as DC, with no inverter, runs longer, because there is no inverter loss (about 85% efficiency) and no idle draw of the inverter itself. A 100 Ah lithium battery at 12.8 V stores about 1,152 Wh usable, so it runs the same 100 W load for roughly twice as long.
The result does not depend on your mains voltage. Whether the inverter puts out 230 V as in Pakistan, the UK and Europe, or 120 V as in the US and Canada, the battery side is the same 12 V and the watts drawn are the same.
100 Ah battery runtime calculator: lead-acid against lithium
The label Ah is not the usable Ah. A 100 Ah lead-acid, AGM or gel battery should only be taken to about 50% of its rating, so only half the energy counts. A 100 Ah lithium (LiFePO4) battery can safely use about 90%, and sits at 12.8 V instead of 12 V, which is why the lithium example below gives about 3 h at 300 W while a lead-acid battery of the same Ah gives much less.
Lead-acid batteries also lose capacity when they are drained fast. The label Ah is measured over about twenty hours; at a load that empties the battery in an hour the real capacity can be a quarter lower. The calculator does not apply this drop, so treat results under about two hours as optimistic.
Worked examples
100 Ah battery with a 100 W load through an inverter
100 Ah × 12 V × 50% = 600 Wh usable. 600 Wh ÷ 148 W from the battery = about 4 h 3 min.
100 Ah battery with a 1,000 W load (microwave or kettle)
The same 600 Wh ÷ 1,206 W from the battery = about 29 min. At this rate the inverter pulls well over eighty amps from the battery, and a lead-acid battery drained this fast gives less than its label Ah, so expect even less in practice.
100 Ah lithium battery with a 300 W load
100 Ah × 12.8 V × 90% = 1,152 Wh usable, which runs 300 W (a TV with a few fans, or a small compressor fridge at full duty) for about 3 h.
12 V compressor fridge, 60 W average, wired as DC
A 12 V camping or car fridge draws more when the compressor runs and nothing when it rests; its average over a day is about 60 W. With inverter efficiency set to one: 100 Ah × 12 V × 50% = 600 Wh, ÷ 60 W from the battery = about 10 h.
200 Ah deep cycle battery with a 500 W load
200 Ah × 12 V × 50% = 1,200 Wh usable. 1,200 Wh ÷ 618 W from the battery = about 1 h 56 min.
Runtime of a 12 V lead-acid battery through an inverter (50% usable, 85% inverter efficiency, 30 W idle draw)
| Battery | Load | Usable energy | Runtime |
|---|---|---|---|
| 100 Ah | 50 W | 600 Wh | 6 h 45 min |
| 100 Ah | 100 W | 600 Wh | 4 h 3 min |
| 100 Ah | 300 W | 600 Wh | 1 h 34 min |
| 100 Ah | 1,000 W | 600 Wh | 29 min |
| 150 Ah | 300 W | 900 Wh | 2 h 21 min |
| 150 Ah | 500 W | 900 Wh | 1 h 27 min |
| 200 Ah | 500 W | 1,200 Wh | 1 h 56 min |
| 200 Ah | 1,000 W | 1,200 Wh | 59 min |
Common mistakes
- Using the full Ah. A lead-acid battery taken below about 50% loses cycles quickly, so only that part counts as usable.
- Forgetting the inverter. An inverter turns about 85% of the battery energy into AC; leave the efficiency at one only for a true DC load.
- Using the fridge's peak watts. A fridge compressor cycles on and off; use the average draw over a day or the runtime will look far too short.
- Trusting the label Ah at high loads. Lead-acid capacity is rated over about twenty hours; a load that empties the battery in an hour or two gets noticeably less.
- Mixing up a car battery with a deep cycle battery. A car starting battery is built for short bursts and is damaged by deep discharge, so set a smaller depth of discharge for it.
Safety: Fuse the battery cable close to the battery, size the cable for the inverter current, keep lead-acid batteries ventilated, and have a licensed electrician connect any inverter to house wiring.
Frequently asked questions
How long will a 12 V battery last?
Divide the usable watt-hours by what the inverter takes from the battery: the load watts ÷ its efficiency, plus its own idle draw. A 100 Ah lead-acid battery has about 600 Wh usable, so it lasts about 4 h 3 min at 100 W, about 1 h 56 min at 500 W if it is a 200 Ah battery, and about 29 min at 1,000 W.
A 100 Ah battery gives how many hours?
About 4 h 3 min at 100 W through an inverter, or about 3 h at 300 W if it is a 12.8 V lithium battery. The hours fall almost in proportion as the load rises.
Can a 12 V 100 Ah battery run a 1,000 W load?
Only briefly: about 29 min on paper, and less in practice because a lead-acid battery drained that fast delivers less than its label Ah. You also need an inverter rated for the load and a thick, fused battery cable for the high current.
Is this a 12 V battery life calculator?
It calculates runtime on one charge, not the life of the battery in years. Battery life depends on how deep and how often you discharge; staying within about 50% for lead-acid and about 90% for lithium is what makes a battery last.
How long will a 12 V battery run a fridge?
Use the fridge's average draw, not its peak. A 12 V compressor fridge averaging about 60 W runs about 10 h on a 100 Ah lead-acid battery wired as DC. A mains fridge through an inverter draws more and also pays the inverter loss.
What is the runtime of a 12 V deep cycle battery?
The same formula applies; deep cycle batteries are simply built to be taken to about 50% repeatedly. A 200 Ah deep cycle battery runs a 500 W load for about 1 h 56 min through an inverter.
How do I work out the discharge time of a 12 V battery?
Discharge time in hours = Ah × 12 V × usable depth of discharge ÷ (load watts ÷ inverter efficiency + the inverter's idle draw). For a DC load drop the inverter efficiency and the idle draw; then usable Wh ÷ watts gives the hours and Ah × depth of discharge ÷ amps gives the same answer.
Sources
- Victron Energy: Lithium Battery Smart 12,8 V datasheet (usable capacity and cycle life by depth of discharge)
- Exide Industries: Inva Tubular inverter battery (rated cycle life)
- Battery University: depth of discharge and cycle life of lead-acid and lithium batteries
- Wattlyst methodology and default values