Wiring Calculators

Wiring calculators pick the copper cable and the MCB for a circuit from its load, its length and the kind of load, and check the voltage drop over the run, for mains and for solar DC. They use IEC current ratings for PVC copper cable; have a licensed electrician confirm the final wiring before any work.

One circuit: cable and breaker size

For one circuit, the wire size calculator gives the copper cable and the MCB size calculator the breaker and its curve; for an air conditioner, the wire size for an AC page has the common case worked out.

  • Wire Size Calculator Pakistan

    Find the right copper wire size for any load and length. Shows mm² and Pakistani 3/29, 7/29, 7/36 sizes with ampere ratings and voltage drop.

  • MCB Size Calculator

    Pick the right MCB size and curve (B, C, D) for lights, sockets, ACs and motors from load watts. Wire and breaker matched safely.

  • Wire Size for 1.5 Ton AC

    Which wire and breaker for a 1.5 ton inverter or non-inverter AC? mm² and 3/29, 7/29 sizes, run length and safety margin, explained.

The whole house: one sheet for every circuit

For the whole house, the home wiring load schedule sizes every circuit on one sheet: cable, MCB and the current on each, from your list of rooms and appliances.

Solar DC and long runs: cable and voltage drop

For solar panels and batteries, the solar DC cable calculator keeps the DC drop low, and the voltage drop calculator checks any cable you already have, AC or DC.

Key facts

  • Wire size = the smallest copper cable whose current rating covers the design current × 1.25 (and the MCB) and whose voltage drop over the run stays under 5% for power circuits or 3% for lighting.
  • MCB rating = the next standard size above the design current (watts ÷ volts ÷ power factor, × 1.25 for motors and compressors); standard domestic MCBs run from 6 A to 63 A.
  • Voltage drop = 2 × length × current × resistivity ÷ area (single-phase and DC) or √3 × length × current × resistivity ÷ area (three-phase), with copper resistivity of 0.0225 Ω·mm²/m at working temperature.

Current rating and voltage drop: two separate checks

A cable must carry the circuit's current without overheating, which sets a minimum size from the current rating table, and it must deliver enough voltage at the far end, which can call for a larger size on a long run. The calculators take the larger of the two, holding lighting circuits to a 3% drop and other circuits to 5%.

Frequently asked questions

What size wire do I need for an AC?

It depends on the AC's current and the length of the run. The AC wire size calculator works out a typical split AC circuit, and the wire size calculator any other load and length.

What is the difference between a type B and a type C MCB?

A type B MCB trips quickly on a short overcurrent and suits lighting circuits; a type C rides through the starting surge of motors and compressors such as pumps and ACs, and is the usual choice for socket circuits, where plugged-in appliances start with a surge. The MCB size calculator picks the curve from the load type.

Is solar DC cable sized the same way?

The same two checks apply, but the current at battery voltage is high and DC runs are held to a lower drop, so DC cables often come out thicker. The solar DC cable calculator sizes them.

Do I still need an electrician?

Yes. These calculators give planning sizes from standard tables; a licensed electrician must confirm the cable, breaker, earthing and installation method on site.

Sources