Generator Size for 1.5 Ton AC

Quick answer: A 1.5 ton inverter AC with 500 W of fans and lights needs a 3.5 kVA generator. A 1.5 ton non-inverter AC needs 7.5 kVA, because its compressor starts at 5,400 W.

A 1.5 ton inverter AC with 500 W of fans and lights needs a 3.5 kVA generator: 1,950 W running, 2,400 W while the compressor starts, 3.05 kVA calculated. A 1.5 ton non-inverter AC with the same load needs 7.5 kVA because its compressor starts at 5,400 W. Generator kVA = max(running watts × margin, starting watts) ÷ power factor ÷ 1,000.

Pick the size and type from the AC nameplate. Inverter ACs start softly; non-inverter ACs have a big compressor surge.

Fans, lights, TV and fridge that will run on the generator at the same time. Set zero for the AC alone.

Advanced settings

Only if the other load includes a motor such as a fridge, water pump or a second AC. Leave blank for fans and lights.

Keeps the generator below full load so it lasts. A decimal like one point two five.

Generators are rated in kVA at this power factor. Leave the default unless the nameplate says otherwise.

Generator size to buy 3.5 kVA
Calculated minimum 3.05 kVA
Total running watts 1,950 W
Peak watts while the AC starts 2,400 W

How the generator size for a 1.5 ton AC is worked out

Split AC 1.5 ton inverter: 1,450 W running, 1,900 W starting (its maximum input). Other load 500 W. Total 1,950 W running and 2,400 W at the moment the AC starts. The larger of 1,950 W × 1.25 margin and 2,400 W is 2,438 W; ÷ 0.8 power factor ÷ 1,000 = 3.05 kVA, rounded up to the next standard size, 3.5 kVA.

P_run = P_ac + P_other; P_peak = P_run + (P_ac_start − P_ac); kVA = max(P_run × m, P_peak) ÷ PF ÷ 1000

  • P_ac = AC running watts, P_ac_start = AC starting watts (compressor surge, or maximum input for an inverter AC)
  • P_other = other appliances running at the same time
  • P_peak = total watts at the moment the largest motor starts
  • m = safety margin on the running load
  • PF = generator power factor (nameplate convention)
  • kVA = generator size; the result is rounded up to the next standard size

What kVA generator runs a 1.5 ton AC?

It depends almost entirely on whether the AC is inverter or non-inverter. An inverter AC ramps its compressor up slowly, so its peak is its maximum rated input, about 1,900 W for 1.5 ton; it runs from a 2.5 kVA generator alone and a 3.5 kVA generator with 500 W of fans and lights.

A non-inverter AC starts its compressor at full speed and draws about 5,400 W for a second or two. The generator must carry that surge, so the same 1.5 ton size needs 7.5 kVA. The surge, not the running watts, sets the size.

Generator size for split ACs with 500 W of fans and lights running at the same time

ACOther loadRunning wattsPeak wattsGenerator to buy
Split AC 1 ton inverter500 W1,400 W1,890 W2.5 kVA
Split AC 1 ton non-inverter500 W1,700 W4,100 W6.5 kVA
Split AC 1.5 ton inverter500 W1,950 W2,400 W3.5 kVA
Split AC 1.5 ton non-inverter500 W2,300 W5,900 W7.5 kVA
Split AC 2 ton inverter500 W2,400 W2,640 W5 kVA
Split AC 2 ton non-inverter500 W2,900 W7,700 W10 kVA
Split AC 1.5 ton inverter0 W1,450 W1,900 W2.5 kVA
Split AC 1.5 ton non-inverter0 W1,800 W5,400 W7.5 kVA

Inverter AC on a generator: why it needs a much smaller set

An inverter AC has no hard compressor start. It draws about 1,450 W on average at full cooling and never more than its maximum input of 1,900 W, so the generator only needs the running load plus the 1.25 margin. Inverter ACs are also more tolerant of the small voltage and frequency swings of a portable generator, though a very cheap generator with poor voltage control can still trip the AC's protection.

If your generator is already bought and is in the 2.5 to 3.5 kVA range, an inverter AC is the only type it can run; a non-inverter 1.5 ton AC will stall it.

Non-inverter AC generator size

The compressor of a 1.5 ton non-inverter AC runs at about 1,800 W and starts at about 5,400 W, which is 3 times its running watts. With 500 W of fans and lights the peak is 5,900 W, or 7.38 kVA, so the generator to buy is 7.5 kVA. A 1 ton non-inverter AC with the same other load needs 6.5 kVA and a 2 ton non-inverter AC needs 10 kVA.

The compressor also restarts every few minutes as the thermostat cycles, so the generator takes that surge all day, not once. A soft starter fitted to the AC lowers the surge, but the calculator assumes a plain direct start, which is what most units have.

The running vs starting watts guide explains why a generator is sized on that start, and the generator fuel consumption calculator shows the litres an hour the set burns at your load.

Generator sizes for different AC setups

1.5 ton inverter AC on its own

Split AC 1.5 ton inverter: 1,450 W running and at most 1,900 W. 1,900 W ÷ 0.8 ÷ 1,000 = 2.38 kVA, so a 2.5 kVA generator runs it.

1.5 ton non-inverter AC with 500 W of fans and lights

Split AC 1.5 ton non-inverter: 1,800 W running but 5,400 W while the compressor starts. With 500 W of other load the total is 2,300 W running and 5,900 W at the start, which is 7.38 kVA; buy a 7.5 kVA generator.

Two 1.5 ton inverter ACs with fans

One Split AC 1.5 ton inverter (1,450 W) plus 1,500 W for the second inverter AC and fans, with the second AC's maximum input entered as the other starting watts: 2,950 W running, 3,400 W peak, 4.61 kVA calculated, so a 5 kVA generator.

1 ton non-inverter AC with 500 W of other load

Split AC 1 ton non-inverter: 1,200 W running, 3,600 W starting. Total 1,700 W running and 4,100 W at the start, 5.13 kVA, so the generator to buy is 6.5 kVA.

2 ton non-inverter AC with 500 W of other load

Split AC 2 ton non-inverter: 2,400 W running, 7,200 W starting. The peak of 7,700 W gives 9.63 kVA, so a 10 kVA generator is needed.

1.5 ton AC generator sizes to remember

  • A 1.5 ton inverter AC runs at about 1,450 W and needs at most 1,900 W, so on its own it runs from a 2.5 kVA generator.
  • A 1.5 ton non-inverter AC runs at about 1,800 W but its compressor draws about 5,400 W for a second or two while starting, which needs a 7.5 kVA generator even with only 500 W of other load.
  • Generator size in kVA = the larger of (running watts × 1.25) or (starting watts) ÷ 0.8 power factor ÷ 1,000, rounded up to the next standard size sold.
  • For one inverter AC with 500 W of fans, lights and an inverter fridge, a 3.5 kVA generator is enough; a non-inverter fridge also starts with a surge, so enter its starting watts, which can move the set up a size; each extra inverter AC adds about 1,450 W of running load.

What kVA generator for a home with an AC?

Add up everything that will run on the generator at the same time and enter it as the other load. Fans, LED lights, a TV, a WiFi router and an inverter fridge typically come to a few hundred watts, which is why 500 W is the default. With one 1.5 ton inverter AC that gives 1,950 W running and a 3.5 kVA generator.

For two inverter ACs, enter the second AC's running watts in the other load and its maximum input as the other starting watts: a 1.5 ton inverter AC plus 1,500 W (a second inverter AC with fans) needs 5 kVA. A fridge or water pump that can start while the AC runs should go in the other starting watts too. Loads such as an iron, geyser or microwave are best kept off while the generator runs the AC.

Mistakes that leave the AC unable to start

  • Sizing for the running watts of a non-inverter AC. Its compressor starts at about 3 times the running watts, and a generator that cannot supply that surge stalls or trips every time the compressor cycles on.
  • Reading kVA as kW. A generator rated in kVA delivers only 80% of that number in watts at the nameplate power factor.
  • Forgetting what else is on. A fridge, water pump or second AC starting while the AC runs adds its own surge; enter it as the other starting watts.
  • Running the generator flat out. The 1.25 margin on the running load is there for engine life, fuel use and the loads people switch on without thinking.
  • Running an AC on a cheap generator with poor voltage control. Inverter ACs tolerate small swings, but a generator that hunts or sags under load can trip the AC's protection or damage its board.

Safety: Earth the generator, connect it to the house only through a proper changeover switch so it can never back-feed the grid, keep it outdoors away from windows, and have a licensed electrician do the wiring.

Generator and AC questions

Can a 5 kVA generator run a 1.5 ton AC?

Yes for an inverter AC: it needs 2.5 kVA alone and 3.5 kVA with 500 W of fans and lights, so a 5 kVA set has room to spare. No for a 1.5 ton non-inverter AC: its 5,400 W compressor surge needs 7.5 kVA.

What is the load of a 1.5 ton AC in kVA?

A 1.5 ton inverter AC runs at about 1,450 W and draws at most 1,900 W, which at the generator power factor of 0.8 is 2.38 kVA: a 2.5 kVA set runs it on its own. A 1.5 ton non-inverter AC starts at 5,400 W, so with 500 W of fans and lights it needs 7.5 kVA.

What size generator do I need for a 1 ton AC?

A 1 ton inverter AC with 500 W of fans and lights runs from a 2.5 kVA generator (see the table). A 1 ton non-inverter AC with the same other load starts at 3,600 W and needs a 6.5 kVA generator.

What size generator do I need for a 2 ton AC?

A 2 ton inverter AC with 500 W of other load needs a 5 kVA generator. A 2 ton non-inverter AC starts at 7,200 W and needs 10 kVA.

Why does a non-inverter AC need such a big generator?

Its compressor starts direct-on-line and pulls about 3 times its running watts for a second or two, 5,400 W for a 1.5 ton unit. The generator must deliver that peak or it stalls, so it is sized on the surge, not on the running watts.

How many kVA of generator for a home with one AC, fans, lights and a fridge?

With a 1.5 ton inverter AC and about 500 W of other load, 3.5 kVA. With a 1.5 ton non-inverter AC, 7.5 kVA. Add the running watts of each extra AC to the other load to size for more.

1.5 ton AC ke liye kitne kVA ka generator chahiye?

Inverter AC aur 500 W pankhon aur lights ke saath 3.5 kVA ka generator kaafi hai. Non-inverter 1.5 ton AC start hote waqt 5,400 W kheenchta hai, is liye us ke liye 7.5 kVA ka generator chahiye.

1 ton aur 2 ton AC ke liye kitna bara generator chahiye?

500 W doosre load ke saath 1 ton inverter AC 2.5 kVA par aur 1 ton non-inverter AC 6.5 kVA par chalta hai. 2 ton inverter AC ke liye 5 kVA aur 2 ton non-inverter AC ke liye 10 kVA chahiye.

Data behind the AC generator sizes

Last updated: