Solar Inverter Error Codes and What to Do

Pick your inverter brand and type the code on the display to see its meaning, likely cause and what you can safely do yourself. The tables come from the manufacturers' manuals for Growatt, Huawei, Solis, GoodWe, Sungrow, Fronius, Inverex Nitrox and the Voltronic Axpert design. If the fix needs the DC side opened, the table says to call the installer.

Type the code as the display shows it, or a word such as battery, fan or grid. 266 codes from manufacturer manuals, last checked .

Key facts

  • An inverter error code is a message from the inverter's own protection: most codes mean the grid, the battery or the PV string is outside the range the inverter accepts, not that the inverter is broken.
  • Many Pakistani hybrid inverters are built on the Voltronic Axpert design, so their fault numbers (fan locked, over temperature, battery voltage too high, output short circuit, overload) follow the Axpert table; check your manual, the numbering can differ by model.
  • Grid-side codes on on-grid inverters (grid voltage or frequency out of range, no grid) clear on their own when the supply returns to normal; a code that returns every afternoon usually means high grid voltage on your street, which the DISCO must fix, not the inverter.
  • Anything that requires opening DC connectors, replacing a fan or a fuse, or changing settings inside the inverter is an installer job; PV strings carry lethal DC voltage whenever the sun is up, even with the AC switched off.
  • Every row in the tables below is Wattlyst's own plain-English summary of the manufacturer's troubleshooting entry, and each brand links to the manual it comes from; check the manual for your exact model before acting.

How to use the error code lookup

Choose the brand, then type the code exactly as the display or app shows it: a number such as 02 or 1010, a letter code such as F03, or a word from the message such as battery, grid or fan. Matching rows stay on screen; everything else hides. Clear the box to see the full table for that brand again.

If your brand is not listed, try the Voltronic Axpert table: Inverex, Crown, Homage, Fronus and several other Pakistani brands use that platform for their hybrid models, and the fault numbers often match. Confirm against the manual that came with your unit before acting.

Inverex, Nitrox and other Pakistani brands

We only list codes we could read in a manufacturer's manual. The Inverex Nitrox table comes from Inverex's own user manual for the three-phase on-grid Nitrox models: it names every F code, gives causes for the grid, solar voltage and earth fault codes, and asks you to contact the distributor if a fault stays after a reset. Manuals for the Inverex Veyron and Aerox hybrids and for Knox were not available with the maker's name on them when this page was checked. Most of those units are Voltronic-based hybrids: start with the Axpert table and your printed manual, and send us a copy of the manual's fault table through the contact page so we can add it with a source.

Growatt's off-grid SPF series uses a fault table very close to Axpert's; Growatt's on-grid MIN series uses three-digit error numbers instead. Both tables are below.

What you can safely check yourself

Safe checks: the AC and DC isolators are on, the battery breaker is on, the display shows the grid voltage within the normal range, the fan vents are not blocked by dust, and the inverter is not in direct sun or a closed cupboard. A restart (AC off, DC off, wait a minute, DC on, AC on, in the order your manual gives) clears many one-off codes.

Call the installer for anything else: repeated over-temperature, insulation or earth-fault codes, arc-fault codes, battery communication errors, a blown fuse or a code that comes back after a restart. Never open the inverter or a DC connector yourself.

Growatt SPF off-grid and hybrid error codes

Growatt SPF (off-grid / hybrid 'ES' series). Models: SPF 3000-6000 ES / ES PLUS (codes table from SPF 6000 ES PLUS manual; same numbering family as other SPF units but verify per model)

CodeMeaningLikely causeWhat to doCall installer?
Fault 01Fan is locked / fan faultThe cooling fan has stopped or is faulty.See that every fan turns freely and is not choked with dust. If a fan is dead it has to be replaced, which is installer work.Yes
Fault 02Over temperatureA part inside the inverter has gone above its safe temperature (about 100 °C).Make sure air can flow around the unit and the room is not too hot, and clear dust from the vents. A loose temperature-sensor plug can also cause it; if the code repeats, call the installer.Usually not
Fault 03Battery voltage is too high (battery over-charged)The battery voltage has risen too high, meaning the battery is being over-charged.Restart the unit. Have the installer check that the battery type, number of batteries and charge settings match the inverter; if it happens again the unit goes to the service centre.Yes
Warning 04Battery voltage / SOC is too low (low battery)The battery voltage, or the lithium battery's state of charge, has fallen too low.Measure the battery voltage at the inverter's DC input (or read the SOC on the screen for lithium) and let the battery recharge from solar or grid.Usually not
Fault 05Output short circuitedThe AC output is short-circuited.Switch off the loads and look for a faulty appliance or a wiring fault on the output side. If the fault stays with the loads off, call the installer.Yes
Fault 06 / 58Output voltage abnormal (too high / too low)The inverter's output voltage has gone outside its normal band (far above or below mains voltage).Reduce the load and restart. If the code repeats, the unit needs the service centre.Yes
Fault 07Overload time outThe load has been above the inverter's rating (about 110%) for longer than it allows.Switch some appliances off so the load is below the inverter's rated power.Usually not
Fault 08Bus voltage is too highThe internal DC bus voltage is too high. With a lithium battery that has no communication cable, the charge voltage settings (programs 19 and 21) may be set too high for that battery.Have the installer check the battery voltage settings, then restart. If the code repeats, the unit needs the service centre.Yes
Fault 09 / 53 / 57Bus soft start failed / inverter soft start failed / current sensor failedAn internal start-up stage or current sensor has failed.Restart the inverter; if the code comes back, the unit needs the maker's service centre.Yes
Warning 15Parallel input utility grid differentIn a parallel system, the inverters do not all see the same grid input.Parallel systems only: the installer should check that every inverter's AC input wiring is connected properly.Yes
Warning 16Parallel input phase errorIn a parallel system, the input phase order is wrong.Installer work: the input phase wiring (S and T) has to be swapped.Yes
Warning 17Parallel output phase lossIn a parallel system, an output phase is missing or set up wrongly.Installer work: all units must have the same parallel setting (single or three-phase, and phase position), and every unit must be switched on.Yes
Warning 20BMS communication errorThe lithium battery is not talking to the inverter.Check the communication cable between the battery and the inverter and that the battery (BMS) protocol chosen in the settings matches the battery.Usually not
Fault 51Over current or surgeAn over-current or surge was detected.Restart the inverter; if the code comes back, the unit needs the maker's service centre.Yes
Fault 52Bus voltage is too lowThe internal DC bus voltage is too low.Restart the inverter; if the code comes back, the unit needs the maker's service centre.Yes
Fault 55Output voltage is unbalanced / over DC voltage in AC outputThe output voltage is unbalanced, or DC voltage has appeared on the AC output.Restart the inverter; if the code comes back, the unit needs the maker's service centre.Yes
Fault 56Battery connection is openThe battery connection is open: a loose cable or a blown fuse. With a lithium battery without communication, the voltage settings (programs 19 and 21) may be too high for that battery.Check the battery cables and fuse (switch off first; a battery can deliver very high current). If the battery is connected properly, restart; if the code repeats, the unit needs the service centre.Yes
Fault 60Negative power faultPower is flowing backwards into the output. Usual causes: the AC output is connected to the grid input, parallel units have different settings (program 8), current-sharing cables are loose, or the neutrals of parallel units are not joined.These are wiring checks for the installer. If they are all correct and the code stays, contact the service centre.Yes
Fault 61PV voltage is too highThe solar (PV) input voltage is above the inverter's limit. The manual lists the code without further detail.The installer must check the panel string voltage against the inverter's maximum PV input.Yes
Fault 62Internal communication errorInternal communication between the inverter's boards has failed. The manual lists the code without further detail.Treat it like other internal faults: Restart the inverter; if the code comes back, the unit needs the maker's service centre.Yes
Fault 80 / 81CAN fault / Host loss (parallel communication)Parallel communication has been lost (CAN fault or host lost).Installer work: check the parallel communication cables and that the parallel setting (program 23) is right. If it stays, contact the service centre.Yes
Warning 01Fan is locked when inverter is onThe fan has stopped while the inverter is running (warning only).Clean dust or anything blocking the fan; if it stays stopped, call the installer.Usually not
Warning 02Over temperatureThe inverter is running hot (warning only).Reduce the load and improve ventilation; see Fault 02.Usually not
Warning 03Battery is over-chargedThe battery is being over-charged (warning only).Have the installer check the battery charge settings (see Fault 03).Yes
Warning 07OverloadThe load is above the inverter's rating (warning only).Switch some appliances off.Usually not
Warning 10Output power deratingThe inverter is cutting its output power to protect itself, usually because of heat or a high PV voltage.Reduce the load and keep the unit cool. The manual gives no further detail.Usually not
Warning 12Solar charger stops due to low batteryThe solar charger has stopped because the battery is too low.Let the battery recharge, from the grid if needed, and check its condition.Usually not
Warning 13Solar charger stops due to high PV voltageThe solar charger has stopped because the PV voltage is too high.The installer must check the panel string configuration.Yes
Warning 14Solar charger stops due to overloadThe solar charger has stopped because it is overloaded.Reduce the charging or load demand.Usually not
Warning 19Battery disconnectThe battery is disconnected.Check that the battery breaker is on and the cables are tight; if unsure, call the installer.Usually not
Warning 21PV power insufficientThere is not enough solar power for the demand.Normal in low sun, early morning, evening or cloud; no action needed.Usually not
Warning 33BMS communication lossThe battery's management system (BMS) has stopped communicating.Check the BMS cable and protocol setting (see Warning 20).Usually not
Warning 34-45Lithium battery BMS alarms: 34 Cell over voltage, 35 Cell under voltage, 36 Total over voltage, 37 Total under voltage, 38 Discharge over voltage, 39 Charge over voltage, 40 Discharge over temperature, 41 Charge over temperature, 42 Mosfet over temperature, 43 Battery over temperature, 44 Battery under temperature, 45 System shut downThese alarms come from the lithium battery's own management system (cell or pack voltage, temperature, or a protective shutdown).The fault is in the battery, not the inverter: contact the battery supplier or installer.Yes

Growatt MIN and MOD on-grid error codes

Growatt MIN / MOD on-grid (TL-X family). Models: MIN 2500-6000TL-X (manual read); MOD/MID share the Error 2xx/4xx numbering family per Growatt but only MIN TL-X was verified

CodeMeaningLikely causeWhat to doCall installer?
Error: 200AFCI fault (DC arc detected)An electric arc has been detected on the DC (solar) side.Switch the inverter off and have the installer check the panel connectors, then restart. If it stays, contact Growatt.Yes
Error: 201 (Residual I High)Leakage current too highLeakage current to earth is too high.Restart the inverter. If the code stays, contact Growatt or the installer.Yes
Warning 202DC SPD function abnormalThe DC surge protection device is not working.After shutdown the installer should check the DC surge protector; if the code stays, contact Growatt.Yes
Warning 203PV1 or PV2 circuit shortA short circuit was found on PV input 1 or 2.The installer should check the panel polarity and restart. If the warning stays, Growatt service replaces the power board.Yes
Warning 204Dry-contact function abnormalThe dry-contact (relay output) function is not working.After shutdown the installer should check the dry-contact wiring; if the code stays, contact Growatt.Yes
Warning 205PV1 or PV2 boost brokenThe boost circuit for PV input 1 or 2 is damaged.Restart. If the warning stays, Growatt service replaces the power board.Yes
Warning 207USB over-currentToo much current is being drawn through the USB port.Unplug the USB stick or monitoring dongle, shut the inverter down, then plug it back in. If the code stays, contact Growatt.Usually not
Warning 401Inverter communicates with meter abnormalThe inverter cannot talk to the energy meter.Check that the meter is powered and that its cable to the inverter is connected properly.Usually not
Error: 402Output high DCI (DC injection in AC output)Too much DC current is appearing in the AC output.Restart the inverter; if it stays, contact Growatt.Yes
Error: 404Bus sample faultThe internal DC bus voltage reading is faulty.Restart the inverter; if it stays, contact Growatt.Yes
Warning 404EEPROM abnormalThe settings memory (EEPROM) is not working properly.Restart. If the warning stays, Growatt service replaces the control (M3) board.Yes
Error: 405Relay faultA grid relay inside the inverter has failed its check.Restart the inverter; if it stays, contact Growatt.Yes
Warning 405Firmware version is not consistentThe firmware versions on the inverter's boards do not match.The firmware needs updating to the matching version by the installer or Growatt service.Yes
Error: 407Auto test failedThe inverter's automatic self-test did not pass.Restart and run the self-test again; if it still fails, contact Growatt.Yes
Error: 408Over temperatureThe inverter is too hot.Improve ventilation and shade first. If the surrounding air is below about 60 °C, restart; if the code stays, contact Growatt.Usually not
Error: 409Bus over voltageThe internal DC bus voltage is too high.Restart the inverter; if it stays, contact Growatt.Yes
Error: 411DSP communicates with M3 abnormal (internal communication)The two control processors inside the inverter cannot communicate.Restart the inverter; if it stays, contact Growatt.Yes
Error: 414EEPROM faultThe settings memory (EEPROM) has failed.Restart the inverter; if it stays, contact Growatt.Yes
Error: 417DSP / redundant M3 sample mismatchThe two processors that measure the same values disagree.Restart the inverter; if it stays, contact Growatt.Yes
Error: 420GFCI faultThe earth-leakage (GFCI) protection has tripped or failed.Restart the inverter; if it stays, contact Growatt or the installer.Yes
Error: 425AFCI self-test faultThe arc-fault detector failed its own self-test.Restart the inverter; if it stays, contact Growatt or the installer.Yes

Huawei SUN2000 L1 error codes

Huawei SUN2000 (L1 single-phase residential). Models: SUN2000-2KTL-L1 to 6KTL-L1 (alarm IDs are shared across SUN2000 families per Huawei, but only the L1 manual was read)

CodeMeaningLikely causeWhat to doCall installer?
2001 High String Input VoltagePV string open-circuit voltage exceeds the inverter maximum (too many modules in series)Too many panels are connected in series, so the string's open-circuit voltage is above what the inverter can take. The cause ID shows which input (1 = PV1, 2 = PV2).Installer work: re-check the string design so its open-circuit voltage stays below the inverter's maximum input voltage.Yes
2002 DC Arc FaultElectric arc on PV string cablesThe solar string cables are arcing or have a poor connection.Do not touch the DC wiring; the installer has to check the string cables and connectors.Yes
2011 String ReversedPV string connected with reversed polarityA solar string is connected with its plus and minus reversed.Installer work: wait until the string current falls to a very low value, switch the DC isolator off, then correct the polarity.Yes
2021 AFCI Check FailureArc-fault detection self-check failedThe arc-fault detection circuit failed its check or is faulty.Switch off the AC output switch and the DC input switch, wait five minutes and switch them back on. If the fault stays, contact the dealer or Huawei support.Yes
2032 Grid FailureNo grid (outage or AC breaker off)There is no grid: a power cut (load-shedding), or the AC circuit is disconnected or its breaker is off.Check for load-shedding and that the inverter's AC breaker is on, and check the AC voltage.Usually not
2033 Grid UndervoltageGrid voltage below lower thresholdThe grid voltage is below the inverter's lower limit, or has stayed low longer than its low-voltage ride-through time.If it happens now and then, the grid dipped and the inverter recovers on its own. If it is frequent, check the grid voltage; if the grid is out of range contact the DISCO. Protection limits may only be changed with the DISCO's consent.Yes
2034 Grid OvervoltageGrid voltage above upper thresholdThe grid voltage is above the inverter's upper limit, or has stayed high longer than its high-voltage ride-through time.Same as 2033: occasional means wait; frequent means check the grid voltage and its peaks and contact the DISCO. Limits change only with the DISCO's consent.Usually not
2036 Grid OverfrequencyGrid frequency too highThe grid frequency is higher than the local grid standard allows.Occasional: the inverter recovers by itself. Frequent: check the grid frequency and contact the DISCO if it is out of range.Usually not
2037 Grid UnderfrequencyGrid frequency too lowThe grid frequency is lower than the local grid standard allows.Occasional: the inverter recovers by itself. Frequent: check the grid frequency and contact the DISCO.Usually not
2038 Unstable Grid FrequencyGrid frequency changing too fastThe grid frequency is changing faster than the local grid standard allows.Occasional: the inverter recovers by itself. Frequent: check the grid frequency and contact the DISCO.Usually not
2039 Output OvercurrentInverter output current exceeded limitA sharp grid voltage drop or a short circuit on the grid made the output current jump past the inverter's limit, so its protection tripped.The inverter recovers once the grid is normal. If it happens often and costs energy, have the output checked for a short circuit; if it stays, contact the dealer or Huawei support.Yes
2040 Output DC Component OverhighToo much DC in AC outputThe DC part of the inverter's output current is above its limit.The inverter normally recovers on its own; if it is frequent, contact the dealer or Huawei support.Yes
2051 Abnormal Residual CurrentLeakage (residual) current too highThe insulation between the solar input side and earth has dropped while running, so residual current is too high.Occasional: a passing external fault, the inverter recovers by itself. Frequent or constant: the installer should measure the string-to-earth resistance.Yes
2062 Low Insulation ResistancePV array insulation to ground too lowThe solar array is shorted to earth, or damp weather has lowered its insulation to earth.Installer work: measure the array's resistance to earth and check the inverter's earth (PE) cable. It often shows after rain; if the resistance is only low in wet weather, the installer can adjust the insulation protection setting in the app.Yes
2063 OvertemperatureInverter too hot (Minor)The inverter is too hot: poor ventilation, a hot room, or the unit itself not working properly.Improve ventilation and cooling. If ventilation and temperature are fine and it stays, contact the dealer or Huawei support.Usually not
2064 Device FaultUnrecoverable internal fault (Cause ID 1-12: boost short/overcurrent, control circuit, inverter circuit, residual current sensor, temperature detection, EEPROM, auxiliary power, grid-tied relay, DC bus over/under-voltage/imbalance)An internal circuit has a fault the inverter cannot clear by itself (the cause ID names the circuit).Switch off the AC output switch and the DC input switch, wait five minutes and switch them back on. If the fault stays, contact the dealer or Huawei support.Yes
2065 Upgrade Failed or Version MismatchFirmware upgrade failedA firmware upgrade did not finish, or the software and hardware versions do not match.Run the upgrade again; if it keeps failing, contact the dealer or Huawei support.Yes
61440 Monitoring Unit FaultyMonitoring (communication) unit faultThe monitoring unit's flash memory is full or damaged.Switch off the AC and DC switches, wait five minutes and switch them on. If it stays, the monitoring board needs replacing by the dealer or Huawei support.Yes
2067 Faulty Power CollectorSmart power sensor (meter) disconnectedThe smart power sensor (meter) is not connected.Check that the meter model set in the inverter matches the meter fitted, that the communication settings match, and that the meter is powered and its RS485 cable connected.Yes
2068 Battery AbnormalBattery fault, disconnected or breaker off (hybrid/LUNA systems)The battery is faulty or disconnected, or its breaker is off while the system is running.If the battery's fault light is on or blinking, contact the battery supplier. Otherwise have the installer check the battery's power, enable and communication cables and that its auxiliary switch is on, then shut down from the app and switch on the battery, AC and DC switches in turn after five minutes. If it stays, contact the dealer or Huawei support.Yes
2070 Active IslandingGrid outage detected (anti-islanding)The inverter has detected a grid outage and stopped exporting (anti-islanding protection).Usually load-shedding: wait for the grid to return and check the grid voltage at the inverter.Usually not
2077 Off-grid output overloadBackup output overloadedThe backup (off-grid) output is overloaded or short-circuited.Switch off loads on the backup circuit and check that the backup load is within the rated power and has no short circuit.Usually not
2080 Abnormal PV Module ConfigurationPV/optimizer string configuration wrong (Cause IDs 2,3,6,7,8,9)The panel or optimizer layout does not meet the inverter's rules, or a module output is reversed or shorted.Installer work: check the number of modules in total and per string, the number of strings, and the module polarity.Yes
2081 Optimizer FaultAn optimizer is faulty (Warning)One of the optimizers is faulty.Open the optimizer screen in the app to see which one and why, and have the installer replace it.Yes
2082 Grid-tied/Off-grid Controller AbnormalBackup Box communication/internal faultThe inverter cannot communicate with the Smart Backup Box, or the box has an internal fault.Shut down from the app, switch off the AC, DC and battery switches, have the installer check the power and RS485 cables between the box and the inverter, and restart after five minutes. If it stays, contact the dealer or Huawei support.Yes

Solis on-grid and hybrid error codes

Solis (Ginlong) on-grid and hybrid. Models: Solis 1P/3P string inverters and RHI/S5/S6 hybrids (article is Solis' complete display-message list; hybrid battery codes not extracted)

CodeMeaningLikely causeWhat to doCall installer?
OV-G-V 01..05 (1010)Grid overvoltageThe grid voltage has been above the first overvoltage limit of the selected grid standard for too long. The variants (01 to 05) cover a short spike, a ten-minute average and a second, higher limit.If it happens once in a while the grid was briefly out of range and the inverter reconnects on its own. If it is frequent, check the grid voltage and frequency, the grid standard set in the inverter, and the AC breaker and output cable. Protection limits may only be changed by Solis service after the DISCO approves.Yes
UN-G-V (1011)Grid undervoltageThe grid voltage is below the limit.Same as OV-G-V: wait if occasional; if frequent, check the grid, the wiring and the protection settings.Yes
OV-G-F (1012)Grid overfrequencyThe grid frequency is above the limit.Same as OV-G-V.Usually not
UN-G-F (1013)Grid underfrequencyThe grid frequency is below the limit.Same as OV-G-V.Usually not
Backfeed_Iac (1014)AC backfeed currentCurrent is flowing back from the AC side into the inverter.Restart the inverter; if it stays, contact Solis service.Yes
NO-Grid (1015)No grid detectedThe inverter cannot detect the grid.Check for load-shedding and that the AC breaker is on, that the grid is connected and normal, and that the right grid standard is set. If the grid is fine and it stays, contact Solis service.Usually not
G-PHASE (1016)Grid 3-phase unbalancedThe three grid phases are unbalanced.Check that the grid is connected properly and is normal; if it is, contact Solis service.Yes
G-F-FLU (1017)Grid frequency fluctuationThe grid frequency is fluctuating abnormally.Check that the grid is connected and normal; if it is, contact Solis service.Usually not
OV-G-I (1018)Grid output overcurrentThe output current to the grid is too high.Check that the grid is connected and normal; if it is, contact Solis service.Yes
IGFOL-F (1019)Grid current tracking errorThe inverter cannot track the grid current correctly.Restart the inverter; if it stays, contact Solis service.Yes
PHASE-FAULT (101A)Abnormal grid phase angleThe grid phase angle is abnormal.Have the installer check the AC wiring and that the phases are 120 degrees apart, then restart. If it stays, contact Solis service.Yes
OV-DC (1020)DC (PV) overvoltageThe solar (DC) input voltage is too high.Installer work: check that the string voltage is below the inverter's maximum input, then restart. If it stays, contact Solis service.Yes
BoostFal (1020)DC boost circuit faultThe DC boost circuit has a fault.Restart the inverter; if it stays, contact Solis service.Yes
OV-BUS (1021)DC bus overvoltageThe internal DC bus voltage is too high.Have the input voltage checked against the maximum, restart, and contact Solis service if it stays.Yes
UNB-BUS (1022)DC bus unbalancedThe internal DC bus and its half-voltage point do not match (bus unbalanced).Restart the inverter; if it stays, contact Solis service.Yes
UN-BUS (1023)DC bus voltage too lowThe internal DC bus voltage is too low.Check whether the input voltage is too low and restart; if it stays, contact Solis service.Yes
DC-INTF. (1027)Abnormal DC input currentThe DC input current is abnormal.Have the installer check the DC wiring for wrong or damaged connections, then restart. If it stays, contact Solis service.Yes
Reve-DC (1028)DC reversely connectedA DC input is connected with reversed polarity.Installer work: check the DC polarity and cable size and the grid standard setting, then restart. If it stays, contact Solis service.Yes
PvMidIso / PVGndRun (1029)PV mid-point low insulation / PV grounded during operationThe insulation at the PV mid-point is low, or a PV terminal is touching earth while running.Installer work. In early morning or after rain it is usually moisture and clears by itself. Otherwise the installer measures each string's resistance to earth (it should be above about 20 kilo-ohm), checks neutral to earth and the software version, then contacts Solis service.Yes
GRID-INTF. (1030)Grid interferenceThe grid voltage waveform is distorted, often where several inverters share one line.The installer may need grid filter settings or to repair equipment downstream, then restart. If it stays, contact Solis service.Yes
INI-FAULT (1031)DSP initializing faultThe control processor failed to start up properly.Restart the inverter; if it stays, contact Solis service.Yes
OV-TEM (1032)Over temperatureThe temperature near the power switches is above its limit (around 90 °C on single-phase and 115 °C on three-phase units).Check the unit is not in direct sun and has the clearance the manual asks for, lower the room temperature, switch off and restart after fifteen minutes. If it stays, contact Solis service.Usually not
PV ISO-PRO 01/02 (1033)Low PV insulation protectionThe insulation of the solar array to earth is too low.Installer work. In early morning, late afternoon or rain it is often normal moisture. Otherwise the installer measures each string's resistance to earth (above about 20 kilo-ohm), checks neutral to earth, updates the software, then contacts Solis service.Yes
ILeak-PRO 01-04 (1034)Leakage current protectionLeakage current to earth is too high. Typical causes: damaged PV cable insulation, wrong cable size, a faulty transformer downstream, wrong rapid-shutdown wiring, wet buried AC cables or poor AC cable; in rain or early morning, ageing panels.Installer work: connect the strings one at a time to find the faulty one. Solis support can sometimes fix it with a remote software update.Yes
RelayChk-FAIL (1035)Relay check failedThe grid relay failed its self-check. The source lists the code without a solution.Restart; if it stays, contact Solis service, as for other internal faults.Yes
Fan Alarm / Fan_H AlarmInternal / external fan faultThe internal or external cooling fan has a fault.Check the fan is not blocked; a replacement is installer work.Yes
Surge AlarmGrid surge recordedA surge on the grid was recorded for service records; it does not stop the inverter.No action needed.Usually not
VgSpdFailAC SPD faultThe AC surge protection device has a fault.Restart the inverter; if it stays, contact Solis service.Yes

GoodWe ES Uniq hybrid error codes

GoodWe (ES Uniq hybrid; F-codes are shared across GoodWe residential inverters). Models: GW ES Uniq 8-12K with LX A/U batteries (manual read); on-grid DNS/MS/SDT and other hybrids (ET/EH) use the same F01-F163 numbering per this manual's 'all PV inverters' wording - verify per model

CodeMeaningLikely causeWhat to doCall installer?
F01 Grid Power OutageNo gridThere is no grid: a power cut, or the AC cable or AC switch is disconnected.The code clears by itself when the grid returns. Check for load-shedding and that the AC switch and cable are connected.Usually not
F02 Grid Overvoltage ProtectionGrid voltage too highThe grid voltage is above the allowed range, or has stayed high longer than the high-voltage ride-through time.If it happens now and then, the grid was briefly out of range and the inverter reconnects on its own. If it is frequent, check the grid voltage; if it is out of range, contact the DISCO. If it does not clear for a long time, check the AC breaker and output cable.Usually not
F03 Grid Undervoltage ProtectionGrid voltage too lowThe grid voltage is below the allowed range, or has stayed low longer than the low-voltage ride-through time.If it happens now and then, the grid was briefly out of range and the inverter reconnects on its own. If it is frequent, check the grid voltage; if it is out of range, contact the DISCO. If it does not clear for a long time, check the AC breaker and output cable.Usually not
F04 Grid Rapid Overvoltage ProtectionSudden grid overvoltageA sudden very high grid voltage, or a fault in the grid voltage measurement, tripped the inverter.If it happens now and then, the grid was briefly out of range and the inverter reconnects on its own. If it is frequent, check the grid voltage; if it is out of range, contact the DISCO. If it does not clear for a long time, check the AC breaker and output cable.Usually not
F05 10min Overvoltage10-minute average grid voltage too highThe grid voltage averaged over ten minutes is above the limit of the grid standard.Check whether the grid voltage stays high for long periods; if it does, contact the DISCO.Usually not
F06 Grid OverfrequencyGrid frequency too highThe grid frequency is above the local grid standard.Occasional: the inverter reconnects by itself. Frequent: check the grid frequency and contact the DISCO. Protection limits change only with the DISCO's consent.Usually not
F07 Grid UnderfrequencyGrid frequency too lowThe grid frequency is below the local grid standard.Same as F06.Usually not
F08 Grid Frequency InstabilityGrid frequency changing too fastThe grid frequency is changing faster than the local grid standard allows.Occasional: the inverter reconnects by itself. Frequent: contact the DISCO.Usually not
F09 Anti-islanding ProtectionGrid lost but voltage held by load; inverter stops grid connectionThe grid has gone off but connected loads are holding up the voltage, so the inverter stops exporting as safety rules require.Occasional: the inverter reconnects by itself. Frequent: contact the DISCO.Usually not
F10 / F11 LVRT / HVRT faultGrid voltage abnormal longer than ride-through timeThe grid voltage stayed abnormal longer than the ride-through time.Occasional: the inverter reconnects by itself. Frequent: check that grid voltage and frequency are in range and stable; if not, contact the DISCO.Usually not
F12 / F13 / F14 / F15 GFCI Protection (30mA / 60mA / 150mA / slow change)Leakage current to groundLeakage current to earth tripped the inverter (the levels shown are the trip thresholds) because the insulation of the input side to earth dropped while running.Occasional: a passing external fault, the inverter recovers by itself. Frequent or lasting: the installer should check the PV string-to-earth resistance.Yes
F16 / F17 DCI Protection Level 1 / 2DC component in AC output too highThe DC part of the inverter's output current is above the allowed limit.If an external fault caused it, the inverter recovers by itself. If it is frequent and cuts generation, contact the dealer or GoodWe service.Yes
F18 Low Insulation ResistancePV or battery insulation to ground too lowThe PV string or battery port is shorted to earth, or long damp weather has lowered the insulation to earth.Installer work: measure the string and battery port resistance to earth and find any short, and check the inverter's earth conductor. If the resistance is only low in rainy weather, the installer can adjust the insulation protection point in the app.Yes
F19 Grounding AbnormalProtective earth not connectedThe inverter's protective earth is not connected, or a grounded PV string is used without an isolation transformer on the output.Installer work: connect the protective earth properly; with a grounded PV string, fit an isolation transformer on the output.Yes
F20 Hard Power Limit ProtectionAbnormal load fluctuationThe load is fluctuating abnormally.If an external cause, the inverter recovers by itself; if frequent, contact the dealer or GoodWe service.Usually not
F21 Internal Comm LossInternal DSP communication timeoutAn internal chip is not powered or has the wrong firmware, so internal communication timed out.Switch off the AC output switch and the DC input switch, wait five minutes and switch them back on. If the fault stays, contact the dealer or GoodWe service.Yes
F22-F27 Generator faults (waveform, abnormal connection, voltage low/high, frequency low/high)Generator input out of rangeThe generator input is outside its limits. This shows all the time when no generator is connected.With no generator connected, ignore it. With a generator it clears by itself once the generator runs normally; off-grid operation is not affected.Usually not
F28 Parallel I/O Self-check AbnormalParallel communication cable / IO chipA parallel communication cable is loose or the parallel I/O chip is damaged.Installer work: secure the parallel communication cable; if the chip is damaged it must be replaced.Yes
F29 Parallel Grid Line ReversedGrid wires reversed between parallel unitsSome parallel units have their grid wires reversed compared with the others.Installer work: reconnect the grid wires correctly.Yes
F30 AC HCT Check AbnormalAC current sensor sampling abnormalThe AC current sensor reading is abnormal.Switch off the AC output switch and the DC input switch, wait five minutes and switch them back on. If the fault stays, contact the dealer or GoodWe service.Yes
F31 GFCI HCT Check AbnormalLeakage current sensor sampling abnormalThe leakage-current sensor reading is abnormal.Switch off the AC output switch and the DC input switch, wait five minutes and switch them back on. If the fault stays, contact the dealer or GoodWe service.Yes
F32 Inverter Internal FailureInternal fault detectedThe inverter has detected an internal fault.Switch off the AC output switch and the DC input switch, wait five minutes and switch them back on. If the fault stays, contact the dealer or GoodWe service.Yes
F33 Flash R/W AbnormalFlash memory read/write errorThe internal flash memory changed unexpectedly or is worn out.Update to the latest firmware; if it stays, contact the dealer or GoodWe service.Yes
F34 AFCI Check FailureArc-fault self-check failedThe arc-fault module did not detect the test arc during its self-check.Switch off the AC output switch and the DC input switch, wait five minutes and switch them back on. If the fault stays, contact the dealer or GoodWe service.Yes
F35 Cabinet OvertemperatureInverter too hotThe inverter is too hot: poor ventilation, a hot room, or the internal fan not working.Improve ventilation and keep the room within the allowed temperature. If both are fine and it stays, contact the dealer or GoodWe service.Usually not
F36 Bus OvervoltageInternal DC bus voltage too highThe internal DC bus voltage is too high, from a high PV voltage or a measurement or transformer problem.Switch off the AC output switch and the DC input switch, wait five minutes and switch them back on. If the fault stays, contact the dealer or GoodWe service.Yes
F37 PV Input OvervoltagePV string voltage above inverter maximumToo many panels are connected in series, so the string's open-circuit voltage is above the inverter's maximum.Installer work: re-design the string so its open-circuit voltage stays below the maximum; the alarm clears once it is correct.Yes
F38 / F39 PV Continuous Hardware / Software OvercurrentPV input overcurrentThe PV input current is too high, from a wrong module configuration or damaged hardware.Switch off the AC output switch and the DC input switch, wait five minutes and switch them back on. If the fault stays, contact the dealer or GoodWe service.Yes

Sungrow SG RS on-grid error codes

Sungrow SG RS single-phase on-grid. Models: SG2.0RS-S / 2.5RS-S / 3.0RS-S / 3.0RS / 3.6RS / 4.0RS / 5.0RS / 6.0RS (manual says the code table covers 'all PV inverters' but only some apply per model)

CodeMeaningLikely causeWhat to doCall installer?
002, 003, 014, 015 Grid OvervoltageGrid voltage too highThe grid voltage is above the protection setting. The inverter normally reconnects once the grid is back to normal.If it repeats, measure the grid voltage and contact the DISCO if it is above the setting, and have the protection settings checked in the app or display. Limits change only with the DISCO's consent. Contact Sungrow service if these are fine and the fault keeps coming.Yes
004, 005 Grid UndervoltageGrid voltage too lowThe grid voltage is below the protection setting. The inverter normally reconnects once the grid is back to normal.If it repeats, measure the grid voltage and contact the DISCO, have the protection settings and the AC cable checked. Contact Sungrow service if these are fine and the fault keeps coming.Yes
008 Grid OverfrequencyGrid frequency too highThe grid frequency is above the protection setting. The inverter normally reconnects by itself.If it repeats, measure the grid frequency and contact the DISCO if it is out of range, and have the protection settings checked. Contact Sungrow service if these are fine and the fault keeps coming.Yes
009 Grid UnderfrequencyGrid frequency too lowThe grid frequency is below the protection setting. The inverter normally reconnects by itself.Same as 008.Usually not
010 Grid Power OutageNo gridThere is no grid. The inverter reconnects when the grid returns.Check for load-shedding and that the AC breaker is on; the installer checks that the AC cable is tight and live and neutral are on the right terminals. Contact Sungrow service if these are fine and the fault keeps coming.Yes
012 Excess Leakage CurrentLeakage current too highLeakage current is too high, often from weak sunlight or a damp setting; the inverter usually reconnects when conditions improve.If conditions are normal and it stays, the installer should check the insulation of the AC and DC cables. Contact Sungrow service if these are fine and the fault keeps coming.Yes
013 Grid AbnormalGrid parameter out of rangeA grid value is outside the set range. The inverter normally reconnects by itself.Measure the grid and contact the DISCO if it is out of range. Contact Sungrow service if these are fine and the fault keeps coming.Usually not
017 Grid Voltage ImbalancePhase voltages differ too much (3-phase)On a three-phase supply, the phase voltages differ too much. The inverter normally reconnects by itself.Measure the phase voltages and contact the DISCO if they differ a lot; the installer can adjust the imbalance setting. Contact Sungrow service if these are fine and the fault keeps coming.Yes
028, 029, 208, 212, 448-479 PV Reverse Connection FaultPV string polarity reversedA PV string is connected with reversed polarity (the code number shows which input or string).Installer work: switch the DC isolator off once the string current is very low and correct the polarity. Contact Sungrow service if these are fine and the fault keeps coming.Yes
037 Excessively High Ambient TemperatureInverter/module too hotThe inverter or its power module is too hot; it restarts once the temperature is normal.Check that the room is not too hot, the unit is well ventilated and out of direct sun (shade it if not), and that the fan runs; a dead fan is replaced. Contact Sungrow service if these are fine and the fault keeps coming.Yes
039 Low System Insulation ResistancePV/battery insulation to ground too lowThe insulation of the system to earth is too low.Installer work. Wait for the inverter to recover; if it repeats, check the insulation protection setting, measure the string and DC cable resistance to earth, re-check in dry weather if it only happens in rain, and check the battery cables. Contact Sungrow service if these are fine and the fault keeps coming.Yes
043 Excessively Low Ambient TemperatureToo cold to operateThe room is too cold for the inverter to run, so it stops.It restarts when the temperature is back within its operating range.Usually not
075 Inverter Parallel Communication AlarmParallel communication cable problemThe parallel communication cable or its terminals have a problem.Installer work: check and reconnect the communication cable. Contact Sungrow service if these are fine and the fault keeps coming.Yes
084 Reverse Connection Alarm of the Meter/CTEnergy meter or CT wired backwardsThe energy meter or current sensor (CT) is wired wrongly or reversed.Installer work: check the meter wiring and its input and output direction, and the rated power setting where an existing inverter is also connected.Yes
088 Electric Arc FaultDC arc detectedAn electric arc was detected on the DC side.Installer work: switch the DC supply off and check for damaged DC cables and loose terminals or fuses, then switch back on and clear the fault in the app or display. Contact Sungrow service if these are fine and the fault keeps coming.Yes
106 Grounding Cable FaultEarth/ground cable problemThe earth cable has a problem.Installer work: check the AC cable connections and the insulation between earth and live. Contact Sungrow service if these are fine and the fault keeps coming.Yes
264-283 MPPT Reverse ConnectionMPPT input polarity reversedAn MPPT input is connected with reversed polarity.Installer work: switch the DC isolator off once the string current is very low and correct the polarity; otherwise contact Sungrow.Yes
323 Grid ConfrontationOutput port connected to a live grid when it should not beThe inverter's output port is connected to a live grid where it should not be.Installer work: disconnect the output from the grid. Contact Sungrow service if these are fine and the fault keeps coming.Yes
332-363 / 364-395 Boost Capacitor Overvoltage Alarm / FaultBoost capacitor overvoltageThe boost capacitor voltage is too high. As an alarm (332-363) the inverter keeps running; as a fault (364-395) it stops.Alarm: check the wiring and terminals and for anything foreign in the unit. Fault: switch off AC, DC and any battery switches, wait fifteen minutes, switch on AC and DC in turn and restart. Contact Sungrow service if these are fine and the fault keeps coming.Yes
514 Meter Communication Abnormal AlarmMeter not communicatingThe energy meter is not communicating.Check and reconnect the meter's communication cable. Contact Sungrow service if these are fine and the fault keeps coming.Yes
532-547, 564-579 PV Reverse Connection AlarmString polarity reversed (alarm level)A PV string has reversed polarity (alarm level; the code shows which string).Same as 028/029.Yes
548-563, 580-595 PV Abnormal AlarmString producing abnormally (shading, loose wiring, fuse)A PV string is producing less than expected: shading or dirt on its modules, loose wiring or a blown DC fuse.You can check for shade and dirt on the panels; wiring and fuses are installer work. Contact Sungrow service if these are fine and the fault keeps coming.Yes
System Fault (007, 011, 016, 019-025, 030-034, 036, 038, 040-042, 044-050, 052-058, 060-069, 085, 087, 092, 093, 100-105, 107-114, 116-124, 200-211, 248-255, 300-322, 324-328, 401-412, 600-603, 605, 608, 612, 616, 620, 622-624, 800, 802, 804, 807, 1096-1122)Internal system faultA general internal system fault.Wait for the inverter to recover. If not, switch off AC, DC and any battery switches, wait fifteen minutes, switch on AC and DC in turn and restart. Contact Sungrow service if these are fine and the fault keeps coming.Yes
System Alarm (059, 070-074, 076-083, 089, 216-218, 220-233, 432-434, 500-513, 515-518, 635-638, 900, 901, 910, 911, 996)Non-blocking system alarmA general system alarm; the inverter keeps running.Check the related wiring and terminals and look for foreign objects or other problems around the unit, and correct them. Contact Sungrow service if these are fine and the fault keeps coming.Yes

Fronius Symo, Primo and GEN24 error codes

Fronius (Symo / Primo SnapINverter STATE codes; GEN24 1xxx codes). Models: Symo Hybrid (online manual read; Class 1-5 codes are shared with Symo/Primo/Galvo SnapINverters per Fronius numbering) and Primo GEN24 7.7/10.0 (GEN24 lists only 1030/1173/1191 in its manual)

CodeMeaningLikely causeWhat to doCall installer?
STATE 102 (also 103, 105, 106, 107, 108, 112)AC (grid) voltage too high; class 1 codes = grid conditions outside permissible rangeThe grid voltage is too high (102). The other class 1 codes in this group cover grid voltage, frequency or islanding conditions outside the allowed range.The inverter waits until the grid has been back in range for a while, then starts again. Check for grid problems; if the code keeps coming back, call the installer.Usually not
STATE 301Overcurrent ACThe AC output current was too high.Feed-in stops for a moment and the inverter starts again. If the code stays on permanently, a Fronius-trained technician is needed.Yes
STATE 302Overcurrent DC or battery not detectedThe DC current is too high, or the battery is not detected.Same as 301.Yes
STATE 303 / 304DC module overtemperature (PV) / AC module overtemperatureThe DC (PV) or AC power module is too hot.Clean the cooling air openings and heat sink. The inverter clears it by itself; if the code keeps coming back, call the installer.Usually not
STATE 305No power being fed in, despite closed relaysThe relays are closed but no power is being fed in.The inverter clears it by itself; if the code keeps coming back, call the installer.Usually not
STATE 306 (Power low)Not enough PV power to feed in (normal at dawn/dusk)There is not enough solar power to feed in and none is being drawn from the battery. At dawn and dusk this is routine, not a fault.Wait for more sunlight.Usually not
STATE 307 (DC low)DC input voltage too low to feed in (normal at night)The DC input voltage is too low to feed in; normal at night.Wait for more sunlight.Usually not
STATE 308Intermediate circuit voltage too highThe internal (intermediate circuit) voltage is too high.The inverter clears it by itself; if the code keeps coming back, call the installer.Usually not
STATE 401Unable to communicate with the power stage setThe inverter cannot communicate with its power stage.It retries by itself and resumes feeding in when it can. If the code stays permanently, a Fronius-trained technician is needed.Yes
STATE 406 / 407 / 408DC module temperature sensor faulty (PV) / AC module temperature sensor faulty / DC component measured in the grid too highA temperature sensor on the DC or AC module is faulty (406, 407), or the DC part measured in the grid is too high (408).If the code keeps coming back, call the installer.Yes
STATE 412Fixed voltage mode selected instead of MPP voltage modeThe inverter is set to a fixed input voltage instead of tracking the best (MPP) voltage, and the fixed value is too low or too high.A setting the installer has to correct.Yes
STATE 416No communication between power stage set and control systemThe power stage and the control system cannot communicate.Same as 401.Yes
STATE 457Grid relay sticking or neutral conductor ground voltage too highA grid relay is sticking, or the neutral-to-earth voltage is too high; the inverter has stopped feeding in.Installer work: check the earthing so the neutral-to-earth voltage stays below 30 V.Yes
STATE 459 / 460 / 461Error recording the measuring signal for the insulation test / DSP reference voltage out of tolerance / DSP data memory errorAn internal check failed: the insulation-test measurement, a processor reference voltage or the processor's data memory. The inverter is not feeding in.If the code stays permanently, a service technician is needed.Yes
STATE 502Insulation fault on solar modules or on the batteryThere is an insulation fault on the solar modules or the battery.If the code keeps coming back, call the installer.Yes
STATE 509No energy fed into the grid in the past 24 hoursNo energy has been fed into the grid in the past 24 hours.Acknowledge the code and check that feed-in is possible: DC switch on, panels not shaded, dirty or covered. If all is fine, call the installer.Usually not
STATE 522DC low (PV), no PV voltage availableThere is no PV voltage (DC low). At night, or in standby, this is normal.No action at night. In the day, check the DC switch; if it is on, call the installer.Usually not
STATE 558Functional incompatibility between PC boardsSome circuit boards in the inverter are not compatible with each other.The inverter firmware needs updating by the installer or Fronius service.Yes
STATE 567Power derating caused by overvoltageOutput power is being reduced because the grid voltage is very high.It clears by itself once the grid voltage is back in range; if it keeps coming back, call the installer.Usually not
1030 WSD Open (GEN24)Wired shutdown chain openThe wired shutdown (WSD) chain is open: a connected device such as a surge protector broke the signal line, or the factory bypass was removed without fitting a trigger device.Installer work: if the surge protector tripped, an authorised specialist must repair the inverter; otherwise refit the bypass or a trigger device, or set the WSD switch to position 1 (primary device).Yes
1173 ArcContinuousFault (GEN24)Repeated DC arc detected; max auto-reconnects reachedAn electric arc was detected on the PV system and the inverter has used up its automatic restarts for the day.Do not just clear it: the whole affected PV system must first be checked for damage, and damaged parts repaired by qualified specialists. Only then is the status confirmed (sensor held three seconds, or in the event log).Yes
1191 AfciDataTransfer (GEN24)Arc identified (info)An electric arc was detected on the PV system (information only).No action needed by itself; if it repeats it becomes 1173.Usually not

Inverex Nitrox on-grid error codes

Inverex Nitrox (on-grid, three-phase). Models: NITROX-12KW, 15KW, 20KW, 25KW and the -3Ph-5G versions (the manual lists all of them)

CodeMeaningLikely causeWhat to doCall installer?
F01DC input polarity reverse faultThe manual gives only the code's name (table 10.1), no cause.Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F02DC insulation impedance permanent faultThe manual gives only the code's name (table 10.1), no cause.Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F03DC leakage current faultThe manual gives only the code's name (table 10.1), no cause.Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F04Ground fault GFDIThe manual gives only the code's name (table 10.1), no cause.Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F05Read the memory errorThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F06Write the memory errorThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F07GFDI blown fuseThe manual gives only the code's name (table 10.1), no cause.Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F08GFDI grounding touch failureThe manual gives only the code's name (table 10.1), no cause.Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F09IGBT damaged by excessive drop voltageThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F10Auxiliary switch power supply failureThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F11AC main contactor errorsThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F12AC auxiliary contactor errorsThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F14DC firmware over currentThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F15AC firmware over currentSurge loads on the grid.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F16GFCI (RCD) AC leakage current faultThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If it trips again, do not keep resetting it: earth leakage can mean a shock risk, so call the installer. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F17Three phase current, over-current faultThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F18AC over current fault of hardwareSurge loads on the grid.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F19All hardware failure synthesisThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F20DC over current fault of the hardwareThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F21DC leakage flow faultThe manual gives only the code's name (table 10.1), no cause.Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F22Crash stop (if there is a stop button)The manual gives only the code's name (table 10.1), no cause.Release the emergency stop button if one is fitted, then restart the inverter. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Usually not
F23AC leakage current is transient over currentGround error, or PV+ or PV- shorted to ground.Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F24DC insulation impedance failurePV+ or PV- to ground resistance is too low.Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F25DC reverse irrigation failureThe manual gives only the code's name (table 10.1), no cause.Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F26The DC busbar is unbalancedLoss of one phase, a poor connection, or inverter hardware damage.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F27DC end insulation errorThe manual gives only the code's name (table 10.1), no cause.Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F28Inverter 1 DC high faultThe manual gives only the code's name (table 10.1), no cause.Do not open the DC (solar) side yourself: a high DC voltage can come from the panel string, and PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F29AC load switch failureThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F30AC main contactor failureThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F31AC secondary contactor failureThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F32Inverter 2 DC high faultThe manual gives only the code's name (table 10.1), no cause.Do not open the DC (solar) side yourself: a high DC voltage can come from the panel string, and PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F33AC over currentThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F34AC current over loadThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F35No AC gridGrid failure.Usually clears by itself when the grid voltage and frequency return to normal (common during loadshedding and low voltage). If it shows every day, ask the installer to check the grid protection settings and the AC cable. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Usually not
F36AC grid phase errorThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F37AC three-phase voltage imbalance failureThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F38AC three-phase current imbalance failureThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F39AC over currentThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F40DC over currentThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F41AC line W,U over voltageGrid voltage or frequency outside the inverter's normal working range.Usually clears by itself when the grid voltage and frequency return to normal (common during loadshedding and low voltage). If it shows every day, ask the installer to check the grid protection settings and the AC cable. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Usually not
F42AC line W,U low voltageGrid voltage or frequency outside the inverter's normal working range.Usually clears by itself when the grid voltage and frequency return to normal (common during loadshedding and low voltage). If it shows every day, ask the installer to check the grid protection settings and the AC cable. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Usually not
F43AC line V,W over voltageGrid voltage or frequency outside the inverter's normal working range.Usually clears by itself when the grid voltage and frequency return to normal (common during loadshedding and low voltage). If it shows every day, ask the installer to check the grid protection settings and the AC cable. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Usually not
F44AC line V,W low voltageGrid voltage or frequency outside the inverter's normal working range.Usually clears by itself when the grid voltage and frequency return to normal (common during loadshedding and low voltage). If it shows every day, ask the installer to check the grid protection settings and the AC cable. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Usually not
F45AC line U,V over voltageGrid voltage or frequency outside the inverter's normal working range.Usually clears by itself when the grid voltage and frequency return to normal (common during loadshedding and low voltage). If it shows every day, ask the installer to check the grid protection settings and the AC cable. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Usually not
F46AC line U,V low voltageGrid voltage or frequency outside the inverter's normal working range.Usually clears by itself when the grid voltage and frequency return to normal (common during loadshedding and low voltage). If it shows every day, ask the installer to check the grid protection settings and the AC cable. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Usually not
F47AC over frequencyGrid voltage or frequency outside the inverter's normal working range.Usually clears by itself when the grid voltage and frequency return to normal (common during loadshedding and low voltage). If it shows every day, ask the installer to check the grid protection settings and the AC cable. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Usually not
F48AC lower frequencyGrid voltage or frequency outside the inverter's normal working range.Usually clears by itself when the grid voltage and frequency return to normal (common during loadshedding and low voltage). If it shows every day, ask the installer to check the grid protection settings and the AC cable. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Usually not
F49U phase grid current DC over currentThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F50V phase grid current DC over currentThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F51W phase grid current DC over currentThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F52AC inductor A phase current DC current highThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F53AC inductor B phase current DC current highThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F54AC inductor C phase current DC current highThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F55DC busbar voltage is too highSolar (PV) over voltage.Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F56DC busbar voltage is too lowSolar (PV) under voltage.Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F57AC reverse irrigationThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F58AC grid U over currentThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F59AC grid V over currentThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F60AC grid W over currentThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F61Reactor A phase over currentThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F62Reactor B phase over currentThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F63Reactor C phase over currentThe manual gives only the code's name (table 10.1), no cause.Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Yes
F64IGBT heat sink high temperatureThe manual gives only the code's name (table 10.1), no cause.Check that the inverter's air vents are not blocked and that it is out of direct sun. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status.Usually not

Voltronic Axpert error codes

Voltronic Power Axpert (base design of many Pakistani rebrands). Models: Axpert VM III 1.5/3/5 kW (manual read). Other Axpert families (VM IV, MKS IV, MAX, MAX II, King) use the same 01-09 / 51-59 numbering with model-specific additions (MAX II adds 11 PV over voltage, 12 DC/DC over current, 13 battery discharge over current, per voltronicpower.com manual listing - not read). Pakistani brands sold as 'Axpert'-type units (e.g. Inverex Axpert, Ziewnic Axpert) are widely reported to be Voltronic OEM units, but no Inverex/Knox manual was fetched to confirm their code tables.

CodeMeaningLikely causeWhat to doCall installer?
Fault 01Fan is locked / fan faultThe cooling fan has failed.Clean dust from the fan; if it does not turn, the installer replaces it.Yes
Fault 02Over temperatureA part inside the inverter is too hot (above about 100 to 120 °C).Make sure air can flow around the unit and the room is not too hot.Usually not
Fault 03Battery voltage is too highThe battery is over-charged or its voltage is too high.Have the installer check that the battery type, number of batteries and charge settings suit the inverter; otherwise the unit needs the service centre.Yes
Fault 04Battery voltage is too lowThe battery voltage is too low (below about 1.91 V per cell at start-up).Recharge the battery; if it will not hold charge, it needs replacing.Usually not
Fault 05Output short circuited (or converter over-temperature)The output is short-circuited, or an internal part has overheated.Switch the loads off and look for a faulty appliance or wiring fault; if it stays, call the installer.Yes
Fault 06 / 58Output voltage too high / too lowThe output voltage is outside its normal band (below about 190 V or above about 260 V).Reduce the load. If it repeats, the unit needs the service centre.Yes
Fault 07Overload time outThe load has been above about 110% of the rating for too long. A PV voltage above the specification also reduces output power and can cause this.Switch some appliances off; if the PV voltage is too high, the installer reduces the number of panels in series.Usually not
Fault 08 / 09 / 53 / 57Bus voltage too high / bus soft start failed / inverter soft start failed / current sensor failedAn internal component has failed.The unit needs the service centre.Yes
Fault 51Over current or surgeAn over-current or surge was detected.Restart the unit; if the code comes back, it needs the service centre.Yes
Fault 52Bus voltage is too lowThe internal DC bus voltage is too low.Restart the unit; if the code comes back, it needs the service centre.Yes
Fault 55Over DC voltage in AC output / output voltage unbalancedThe output voltage is unbalanced.Restart the unit; if the code comes back, it needs the service centre.Yes
Fault 59PV voltage is over limitationThe PV input voltage is above the specification.Installer work: reduce the number of panels in series.Yes
Warning 01Fan is locked when inverter is on (beep three times every second)Fan warning.Check that the fan turns freely; if it stays, call the installer.Usually not
Warning 02Over temperature (no beep)Over-temperature warning.Reduce the load and improve ventilation.Usually not
Warning 03Battery is over-charged (beep once every second)Battery over-charge warning.Have the installer check the charger and battery settings.Yes
Warning 04Low battery (beep once every second)Low battery warning.Recharge the battery and reduce the load.Usually not
Warning 07Overload (beep once every 0.5 second)Overload warning.Switch some loads off.Usually not
Warning 10Output power derating (beep twice every 3 seconds)Output power is being reduced (derating).Reduce the load; see Fault 07 on derating from a high PV voltage.Usually not
Warning 15PV energy is low (beep twice every 3 seconds)Solar power is low.Normal in low sun; no action needed.Usually not
Warning 16High AC input (>280VAC) during BUS soft startThe grid (utility) voltage is out of range.Wait for the grid voltage to settle; if it is frequent, the installer checks the input voltage.Usually not
Warning 32Communication failure between inverter and remote display panelThe display panel is not communicating.Check the display cable; if it stays, call the installer.Usually not
Warning (battery icon)Battery is not connected / Battery equalizationThe battery is disconnected; the relay may click on and off repeatedly.Check that the battery cables are connected tightly (switch off first).Usually not

Common mistakes

  • Restarting again and again. A code that returns after one restart has a cause; repeated restarts can damage the inverter.
  • Ignoring grid over-voltage codes. If the inverter trips every afternoon, log the voltage it shows and report it to the DISCO; the inverter is doing its job.
  • Reading another brand's table as your own. Fault numbers differ between platforms; use your brand's table or your printed manual.
  • Opening DC connectors with the sun up. PV strings are live whenever there is light; only an installer with the right tools should touch them.

Safety: PV strings and batteries carry dangerous DC voltage and current. Switch off AC and DC isolators in the order your manual gives before touching anything, and leave any work inside the inverter or on the DC side to a licensed electrician or your installer.

Frequently asked questions

What does a solar inverter error code mean?

It is the inverter reporting which protection tripped: grid voltage or frequency out of range, PV voltage too high, battery too low or too high, over temperature, overload, insulation fault and so on. Pick your brand above and type the code to read the manufacturer's meaning and remedy.

My Inverex error code is not in the list. What now?

If you have a Nitrox on-grid inverter, pick Inverex Nitrox in the brand list: every F code from its manual is there. Manuals for the Inverex Veyron and Aerox hybrids were not available with Inverex's name on them when we checked, so those codes are not listed yet. Most of these hybrids follow the Voltronic Axpert table; compare the number there and with your printed manual, and send us the manual's fault table through the contact page so we can add it.

Why does my on-grid inverter stop every afternoon with a grid voltage code?

The street voltage rises when many solar systems export at once and the inverter must disconnect above its limit. Note the voltage shown on the display and report it to your DISCO; an installer can also check the AC cable size and connections, which add to the voltage the inverter sees.

Can I clear an error code by restarting the inverter?

Often, for a one-off trip. Switch off AC then DC, wait about a minute, switch on in the order your manual gives. If the code returns, stop restarting and call the installer.

Which codes mean the battery is the problem?

Battery voltage high or low, battery over-current, battery over-temperature and battery communication (BMS) errors. Check the battery breaker and connections are tight and the battery is not flat; lithium batteries also need the communication cable in place.

Where do these tables come from?

From the manufacturers' own manuals and support pages, listed under Sources with a link for each brand and the date we last checked them. Each row is our own plain-English summary of the manual's entry, not a copy of it.