Solar Inverter Error Codes and What to Do
Pick your inverter brand and type the code on the display to see its meaning, likely cause and what you can safely do yourself. The tables come from the manufacturers' manuals for Growatt, Huawei, Solis, GoodWe, Sungrow, Fronius, Inverex Nitrox and the Voltronic Axpert design. If the fix needs the DC side opened, the table says to call the installer.
Key facts
- An inverter error code is a message from the inverter's own protection: most codes mean the grid, the battery or the PV string is outside the range the inverter accepts, not that the inverter is broken.
- Many Pakistani hybrid inverters are built on the Voltronic Axpert design, so their fault numbers (fan locked, over temperature, battery voltage too high, output short circuit, overload) follow the Axpert table; check your manual, the numbering can differ by model.
- Grid-side codes on on-grid inverters (grid voltage or frequency out of range, no grid) clear on their own when the supply returns to normal; a code that returns every afternoon usually means high grid voltage on your street, which the DISCO must fix, not the inverter.
- Anything that requires opening DC connectors, replacing a fan or a fuse, or changing settings inside the inverter is an installer job; PV strings carry lethal DC voltage whenever the sun is up, even with the AC switched off.
- Every row in the tables below is Wattlyst's own plain-English summary of the manufacturer's troubleshooting entry, and each brand links to the manual it comes from; check the manual for your exact model before acting.
How to use the error code lookup
Choose the brand, then type the code exactly as the display or app shows it: a number such as 02 or 1010, a letter code such as F03, or a word from the message such as battery, grid or fan. Matching rows stay on screen; everything else hides. Clear the box to see the full table for that brand again.
If your brand is not listed, try the Voltronic Axpert table: Inverex, Crown, Homage, Fronus and several other Pakistani brands use that platform for their hybrid models, and the fault numbers often match. Confirm against the manual that came with your unit before acting.
Inverex, Nitrox and other Pakistani brands
We only list codes we could read in a manufacturer's manual. The Inverex Nitrox table comes from Inverex's own user manual for the three-phase on-grid Nitrox models: it names every F code, gives causes for the grid, solar voltage and earth fault codes, and asks you to contact the distributor if a fault stays after a reset. Manuals for the Inverex Veyron and Aerox hybrids and for Knox were not available with the maker's name on them when this page was checked. Most of those units are Voltronic-based hybrids: start with the Axpert table and your printed manual, and send us a copy of the manual's fault table through the contact page so we can add it with a source.
Growatt's off-grid SPF series uses a fault table very close to Axpert's; Growatt's on-grid MIN series uses three-digit error numbers instead. Both tables are below.
What you can safely check yourself
Safe checks: the AC and DC isolators are on, the battery breaker is on, the display shows the grid voltage within the normal range, the fan vents are not blocked by dust, and the inverter is not in direct sun or a closed cupboard. A restart (AC off, DC off, wait a minute, DC on, AC on, in the order your manual gives) clears many one-off codes.
Call the installer for anything else: repeated over-temperature, insulation or earth-fault codes, arc-fault codes, battery communication errors, a blown fuse or a code that comes back after a restart. Never open the inverter or a DC connector yourself.
Growatt SPF off-grid and hybrid error codes
Growatt SPF (off-grid / hybrid 'ES' series). Models: SPF 3000-6000 ES / ES PLUS (codes table from SPF 6000 ES PLUS manual; same numbering family as other SPF units but verify per model)
| Code | Meaning | Likely cause | What to do | Call installer? |
|---|---|---|---|---|
| Fault 01 | Fan is locked / fan fault | The cooling fan has stopped or is faulty. | See that every fan turns freely and is not choked with dust. If a fan is dead it has to be replaced, which is installer work. | Yes |
| Fault 02 | Over temperature | A part inside the inverter has gone above its safe temperature (about 100 °C). | Make sure air can flow around the unit and the room is not too hot, and clear dust from the vents. A loose temperature-sensor plug can also cause it; if the code repeats, call the installer. | Usually not |
| Fault 03 | Battery voltage is too high (battery over-charged) | The battery voltage has risen too high, meaning the battery is being over-charged. | Restart the unit. Have the installer check that the battery type, number of batteries and charge settings match the inverter; if it happens again the unit goes to the service centre. | Yes |
| Warning 04 | Battery voltage / SOC is too low (low battery) | The battery voltage, or the lithium battery's state of charge, has fallen too low. | Measure the battery voltage at the inverter's DC input (or read the SOC on the screen for lithium) and let the battery recharge from solar or grid. | Usually not |
| Fault 05 | Output short circuited | The AC output is short-circuited. | Switch off the loads and look for a faulty appliance or a wiring fault on the output side. If the fault stays with the loads off, call the installer. | Yes |
| Fault 06 / 58 | Output voltage abnormal (too high / too low) | The inverter's output voltage has gone outside its normal band (far above or below mains voltage). | Reduce the load and restart. If the code repeats, the unit needs the service centre. | Yes |
| Fault 07 | Overload time out | The load has been above the inverter's rating (about 110%) for longer than it allows. | Switch some appliances off so the load is below the inverter's rated power. | Usually not |
| Fault 08 | Bus voltage is too high | The internal DC bus voltage is too high. With a lithium battery that has no communication cable, the charge voltage settings (programs 19 and 21) may be set too high for that battery. | Have the installer check the battery voltage settings, then restart. If the code repeats, the unit needs the service centre. | Yes |
| Fault 09 / 53 / 57 | Bus soft start failed / inverter soft start failed / current sensor failed | An internal start-up stage or current sensor has failed. | Restart the inverter; if the code comes back, the unit needs the maker's service centre. | Yes |
| Warning 15 | Parallel input utility grid different | In a parallel system, the inverters do not all see the same grid input. | Parallel systems only: the installer should check that every inverter's AC input wiring is connected properly. | Yes |
| Warning 16 | Parallel input phase error | In a parallel system, the input phase order is wrong. | Installer work: the input phase wiring (S and T) has to be swapped. | Yes |
| Warning 17 | Parallel output phase loss | In a parallel system, an output phase is missing or set up wrongly. | Installer work: all units must have the same parallel setting (single or three-phase, and phase position), and every unit must be switched on. | Yes |
| Warning 20 | BMS communication error | The lithium battery is not talking to the inverter. | Check the communication cable between the battery and the inverter and that the battery (BMS) protocol chosen in the settings matches the battery. | Usually not |
| Fault 51 | Over current or surge | An over-current or surge was detected. | Restart the inverter; if the code comes back, the unit needs the maker's service centre. | Yes |
| Fault 52 | Bus voltage is too low | The internal DC bus voltage is too low. | Restart the inverter; if the code comes back, the unit needs the maker's service centre. | Yes |
| Fault 55 | Output voltage is unbalanced / over DC voltage in AC output | The output voltage is unbalanced, or DC voltage has appeared on the AC output. | Restart the inverter; if the code comes back, the unit needs the maker's service centre. | Yes |
| Fault 56 | Battery connection is open | The battery connection is open: a loose cable or a blown fuse. With a lithium battery without communication, the voltage settings (programs 19 and 21) may be too high for that battery. | Check the battery cables and fuse (switch off first; a battery can deliver very high current). If the battery is connected properly, restart; if the code repeats, the unit needs the service centre. | Yes |
| Fault 60 | Negative power fault | Power is flowing backwards into the output. Usual causes: the AC output is connected to the grid input, parallel units have different settings (program 8), current-sharing cables are loose, or the neutrals of parallel units are not joined. | These are wiring checks for the installer. If they are all correct and the code stays, contact the service centre. | Yes |
| Fault 61 | PV voltage is too high | The solar (PV) input voltage is above the inverter's limit. The manual lists the code without further detail. | The installer must check the panel string voltage against the inverter's maximum PV input. | Yes |
| Fault 62 | Internal communication error | Internal communication between the inverter's boards has failed. The manual lists the code without further detail. | Treat it like other internal faults: Restart the inverter; if the code comes back, the unit needs the maker's service centre. | Yes |
| Fault 80 / 81 | CAN fault / Host loss (parallel communication) | Parallel communication has been lost (CAN fault or host lost). | Installer work: check the parallel communication cables and that the parallel setting (program 23) is right. If it stays, contact the service centre. | Yes |
| Warning 01 | Fan is locked when inverter is on | The fan has stopped while the inverter is running (warning only). | Clean dust or anything blocking the fan; if it stays stopped, call the installer. | Usually not |
| Warning 02 | Over temperature | The inverter is running hot (warning only). | Reduce the load and improve ventilation; see Fault 02. | Usually not |
| Warning 03 | Battery is over-charged | The battery is being over-charged (warning only). | Have the installer check the battery charge settings (see Fault 03). | Yes |
| Warning 07 | Overload | The load is above the inverter's rating (warning only). | Switch some appliances off. | Usually not |
| Warning 10 | Output power derating | The inverter is cutting its output power to protect itself, usually because of heat or a high PV voltage. | Reduce the load and keep the unit cool. The manual gives no further detail. | Usually not |
| Warning 12 | Solar charger stops due to low battery | The solar charger has stopped because the battery is too low. | Let the battery recharge, from the grid if needed, and check its condition. | Usually not |
| Warning 13 | Solar charger stops due to high PV voltage | The solar charger has stopped because the PV voltage is too high. | The installer must check the panel string configuration. | Yes |
| Warning 14 | Solar charger stops due to overload | The solar charger has stopped because it is overloaded. | Reduce the charging or load demand. | Usually not |
| Warning 19 | Battery disconnect | The battery is disconnected. | Check that the battery breaker is on and the cables are tight; if unsure, call the installer. | Usually not |
| Warning 21 | PV power insufficient | There is not enough solar power for the demand. | Normal in low sun, early morning, evening or cloud; no action needed. | Usually not |
| Warning 33 | BMS communication loss | The battery's management system (BMS) has stopped communicating. | Check the BMS cable and protocol setting (see Warning 20). | Usually not |
| Warning 34-45 | Lithium battery BMS alarms: 34 Cell over voltage, 35 Cell under voltage, 36 Total over voltage, 37 Total under voltage, 38 Discharge over voltage, 39 Charge over voltage, 40 Discharge over temperature, 41 Charge over temperature, 42 Mosfet over temperature, 43 Battery over temperature, 44 Battery under temperature, 45 System shut down | These alarms come from the lithium battery's own management system (cell or pack voltage, temperature, or a protective shutdown). | The fault is in the battery, not the inverter: contact the battery supplier or installer. | Yes |
Growatt MIN and MOD on-grid error codes
Growatt MIN / MOD on-grid (TL-X family). Models: MIN 2500-6000TL-X (manual read); MOD/MID share the Error 2xx/4xx numbering family per Growatt but only MIN TL-X was verified
| Code | Meaning | Likely cause | What to do | Call installer? |
|---|---|---|---|---|
| Error: 200 | AFCI fault (DC arc detected) | An electric arc has been detected on the DC (solar) side. | Switch the inverter off and have the installer check the panel connectors, then restart. If it stays, contact Growatt. | Yes |
| Error: 201 (Residual I High) | Leakage current too high | Leakage current to earth is too high. | Restart the inverter. If the code stays, contact Growatt or the installer. | Yes |
| Warning 202 | DC SPD function abnormal | The DC surge protection device is not working. | After shutdown the installer should check the DC surge protector; if the code stays, contact Growatt. | Yes |
| Warning 203 | PV1 or PV2 circuit short | A short circuit was found on PV input 1 or 2. | The installer should check the panel polarity and restart. If the warning stays, Growatt service replaces the power board. | Yes |
| Warning 204 | Dry-contact function abnormal | The dry-contact (relay output) function is not working. | After shutdown the installer should check the dry-contact wiring; if the code stays, contact Growatt. | Yes |
| Warning 205 | PV1 or PV2 boost broken | The boost circuit for PV input 1 or 2 is damaged. | Restart. If the warning stays, Growatt service replaces the power board. | Yes |
| Warning 207 | USB over-current | Too much current is being drawn through the USB port. | Unplug the USB stick or monitoring dongle, shut the inverter down, then plug it back in. If the code stays, contact Growatt. | Usually not |
| Warning 401 | Inverter communicates with meter abnormal | The inverter cannot talk to the energy meter. | Check that the meter is powered and that its cable to the inverter is connected properly. | Usually not |
| Error: 402 | Output high DCI (DC injection in AC output) | Too much DC current is appearing in the AC output. | Restart the inverter; if it stays, contact Growatt. | Yes |
| Error: 404 | Bus sample fault | The internal DC bus voltage reading is faulty. | Restart the inverter; if it stays, contact Growatt. | Yes |
| Warning 404 | EEPROM abnormal | The settings memory (EEPROM) is not working properly. | Restart. If the warning stays, Growatt service replaces the control (M3) board. | Yes |
| Error: 405 | Relay fault | A grid relay inside the inverter has failed its check. | Restart the inverter; if it stays, contact Growatt. | Yes |
| Warning 405 | Firmware version is not consistent | The firmware versions on the inverter's boards do not match. | The firmware needs updating to the matching version by the installer or Growatt service. | Yes |
| Error: 407 | Auto test failed | The inverter's automatic self-test did not pass. | Restart and run the self-test again; if it still fails, contact Growatt. | Yes |
| Error: 408 | Over temperature | The inverter is too hot. | Improve ventilation and shade first. If the surrounding air is below about 60 °C, restart; if the code stays, contact Growatt. | Usually not |
| Error: 409 | Bus over voltage | The internal DC bus voltage is too high. | Restart the inverter; if it stays, contact Growatt. | Yes |
| Error: 411 | DSP communicates with M3 abnormal (internal communication) | The two control processors inside the inverter cannot communicate. | Restart the inverter; if it stays, contact Growatt. | Yes |
| Error: 414 | EEPROM fault | The settings memory (EEPROM) has failed. | Restart the inverter; if it stays, contact Growatt. | Yes |
| Error: 417 | DSP / redundant M3 sample mismatch | The two processors that measure the same values disagree. | Restart the inverter; if it stays, contact Growatt. | Yes |
| Error: 420 | GFCI fault | The earth-leakage (GFCI) protection has tripped or failed. | Restart the inverter; if it stays, contact Growatt or the installer. | Yes |
| Error: 425 | AFCI self-test fault | The arc-fault detector failed its own self-test. | Restart the inverter; if it stays, contact Growatt or the installer. | Yes |
Huawei SUN2000 L1 error codes
Huawei SUN2000 (L1 single-phase residential). Models: SUN2000-2KTL-L1 to 6KTL-L1 (alarm IDs are shared across SUN2000 families per Huawei, but only the L1 manual was read)
| Code | Meaning | Likely cause | What to do | Call installer? |
|---|---|---|---|---|
| 2001 High String Input Voltage | PV string open-circuit voltage exceeds the inverter maximum (too many modules in series) | Too many panels are connected in series, so the string's open-circuit voltage is above what the inverter can take. The cause ID shows which input (1 = PV1, 2 = PV2). | Installer work: re-check the string design so its open-circuit voltage stays below the inverter's maximum input voltage. | Yes |
| 2002 DC Arc Fault | Electric arc on PV string cables | The solar string cables are arcing or have a poor connection. | Do not touch the DC wiring; the installer has to check the string cables and connectors. | Yes |
| 2011 String Reversed | PV string connected with reversed polarity | A solar string is connected with its plus and minus reversed. | Installer work: wait until the string current falls to a very low value, switch the DC isolator off, then correct the polarity. | Yes |
| 2021 AFCI Check Failure | Arc-fault detection self-check failed | The arc-fault detection circuit failed its check or is faulty. | Switch off the AC output switch and the DC input switch, wait five minutes and switch them back on. If the fault stays, contact the dealer or Huawei support. | Yes |
| 2032 Grid Failure | No grid (outage or AC breaker off) | There is no grid: a power cut (load-shedding), or the AC circuit is disconnected or its breaker is off. | Check for load-shedding and that the inverter's AC breaker is on, and check the AC voltage. | Usually not |
| 2033 Grid Undervoltage | Grid voltage below lower threshold | The grid voltage is below the inverter's lower limit, or has stayed low longer than its low-voltage ride-through time. | If it happens now and then, the grid dipped and the inverter recovers on its own. If it is frequent, check the grid voltage; if the grid is out of range contact the DISCO. Protection limits may only be changed with the DISCO's consent. | Yes |
| 2034 Grid Overvoltage | Grid voltage above upper threshold | The grid voltage is above the inverter's upper limit, or has stayed high longer than its high-voltage ride-through time. | Same as 2033: occasional means wait; frequent means check the grid voltage and its peaks and contact the DISCO. Limits change only with the DISCO's consent. | Usually not |
| 2036 Grid Overfrequency | Grid frequency too high | The grid frequency is higher than the local grid standard allows. | Occasional: the inverter recovers by itself. Frequent: check the grid frequency and contact the DISCO if it is out of range. | Usually not |
| 2037 Grid Underfrequency | Grid frequency too low | The grid frequency is lower than the local grid standard allows. | Occasional: the inverter recovers by itself. Frequent: check the grid frequency and contact the DISCO. | Usually not |
| 2038 Unstable Grid Frequency | Grid frequency changing too fast | The grid frequency is changing faster than the local grid standard allows. | Occasional: the inverter recovers by itself. Frequent: check the grid frequency and contact the DISCO. | Usually not |
| 2039 Output Overcurrent | Inverter output current exceeded limit | A sharp grid voltage drop or a short circuit on the grid made the output current jump past the inverter's limit, so its protection tripped. | The inverter recovers once the grid is normal. If it happens often and costs energy, have the output checked for a short circuit; if it stays, contact the dealer or Huawei support. | Yes |
| 2040 Output DC Component Overhigh | Too much DC in AC output | The DC part of the inverter's output current is above its limit. | The inverter normally recovers on its own; if it is frequent, contact the dealer or Huawei support. | Yes |
| 2051 Abnormal Residual Current | Leakage (residual) current too high | The insulation between the solar input side and earth has dropped while running, so residual current is too high. | Occasional: a passing external fault, the inverter recovers by itself. Frequent or constant: the installer should measure the string-to-earth resistance. | Yes |
| 2062 Low Insulation Resistance | PV array insulation to ground too low | The solar array is shorted to earth, or damp weather has lowered its insulation to earth. | Installer work: measure the array's resistance to earth and check the inverter's earth (PE) cable. It often shows after rain; if the resistance is only low in wet weather, the installer can adjust the insulation protection setting in the app. | Yes |
| 2063 Overtemperature | Inverter too hot (Minor) | The inverter is too hot: poor ventilation, a hot room, or the unit itself not working properly. | Improve ventilation and cooling. If ventilation and temperature are fine and it stays, contact the dealer or Huawei support. | Usually not |
| 2064 Device Fault | Unrecoverable internal fault (Cause ID 1-12: boost short/overcurrent, control circuit, inverter circuit, residual current sensor, temperature detection, EEPROM, auxiliary power, grid-tied relay, DC bus over/under-voltage/imbalance) | An internal circuit has a fault the inverter cannot clear by itself (the cause ID names the circuit). | Switch off the AC output switch and the DC input switch, wait five minutes and switch them back on. If the fault stays, contact the dealer or Huawei support. | Yes |
| 2065 Upgrade Failed or Version Mismatch | Firmware upgrade failed | A firmware upgrade did not finish, or the software and hardware versions do not match. | Run the upgrade again; if it keeps failing, contact the dealer or Huawei support. | Yes |
| 61440 Monitoring Unit Faulty | Monitoring (communication) unit fault | The monitoring unit's flash memory is full or damaged. | Switch off the AC and DC switches, wait five minutes and switch them on. If it stays, the monitoring board needs replacing by the dealer or Huawei support. | Yes |
| 2067 Faulty Power Collector | Smart power sensor (meter) disconnected | The smart power sensor (meter) is not connected. | Check that the meter model set in the inverter matches the meter fitted, that the communication settings match, and that the meter is powered and its RS485 cable connected. | Yes |
| 2068 Battery Abnormal | Battery fault, disconnected or breaker off (hybrid/LUNA systems) | The battery is faulty or disconnected, or its breaker is off while the system is running. | If the battery's fault light is on or blinking, contact the battery supplier. Otherwise have the installer check the battery's power, enable and communication cables and that its auxiliary switch is on, then shut down from the app and switch on the battery, AC and DC switches in turn after five minutes. If it stays, contact the dealer or Huawei support. | Yes |
| 2070 Active Islanding | Grid outage detected (anti-islanding) | The inverter has detected a grid outage and stopped exporting (anti-islanding protection). | Usually load-shedding: wait for the grid to return and check the grid voltage at the inverter. | Usually not |
| 2077 Off-grid output overload | Backup output overloaded | The backup (off-grid) output is overloaded or short-circuited. | Switch off loads on the backup circuit and check that the backup load is within the rated power and has no short circuit. | Usually not |
| 2080 Abnormal PV Module Configuration | PV/optimizer string configuration wrong (Cause IDs 2,3,6,7,8,9) | The panel or optimizer layout does not meet the inverter's rules, or a module output is reversed or shorted. | Installer work: check the number of modules in total and per string, the number of strings, and the module polarity. | Yes |
| 2081 Optimizer Fault | An optimizer is faulty (Warning) | One of the optimizers is faulty. | Open the optimizer screen in the app to see which one and why, and have the installer replace it. | Yes |
| 2082 Grid-tied/Off-grid Controller Abnormal | Backup Box communication/internal fault | The inverter cannot communicate with the Smart Backup Box, or the box has an internal fault. | Shut down from the app, switch off the AC, DC and battery switches, have the installer check the power and RS485 cables between the box and the inverter, and restart after five minutes. If it stays, contact the dealer or Huawei support. | Yes |
Solis on-grid and hybrid error codes
Solis (Ginlong) on-grid and hybrid. Models: Solis 1P/3P string inverters and RHI/S5/S6 hybrids (article is Solis' complete display-message list; hybrid battery codes not extracted)
| Code | Meaning | Likely cause | What to do | Call installer? |
|---|---|---|---|---|
| OV-G-V 01..05 (1010) | Grid overvoltage | The grid voltage has been above the first overvoltage limit of the selected grid standard for too long. The variants (01 to 05) cover a short spike, a ten-minute average and a second, higher limit. | If it happens once in a while the grid was briefly out of range and the inverter reconnects on its own. If it is frequent, check the grid voltage and frequency, the grid standard set in the inverter, and the AC breaker and output cable. Protection limits may only be changed by Solis service after the DISCO approves. | Yes |
| UN-G-V (1011) | Grid undervoltage | The grid voltage is below the limit. | Same as OV-G-V: wait if occasional; if frequent, check the grid, the wiring and the protection settings. | Yes |
| OV-G-F (1012) | Grid overfrequency | The grid frequency is above the limit. | Same as OV-G-V. | Usually not |
| UN-G-F (1013) | Grid underfrequency | The grid frequency is below the limit. | Same as OV-G-V. | Usually not |
| Backfeed_Iac (1014) | AC backfeed current | Current is flowing back from the AC side into the inverter. | Restart the inverter; if it stays, contact Solis service. | Yes |
| NO-Grid (1015) | No grid detected | The inverter cannot detect the grid. | Check for load-shedding and that the AC breaker is on, that the grid is connected and normal, and that the right grid standard is set. If the grid is fine and it stays, contact Solis service. | Usually not |
| G-PHASE (1016) | Grid 3-phase unbalanced | The three grid phases are unbalanced. | Check that the grid is connected properly and is normal; if it is, contact Solis service. | Yes |
| G-F-FLU (1017) | Grid frequency fluctuation | The grid frequency is fluctuating abnormally. | Check that the grid is connected and normal; if it is, contact Solis service. | Usually not |
| OV-G-I (1018) | Grid output overcurrent | The output current to the grid is too high. | Check that the grid is connected and normal; if it is, contact Solis service. | Yes |
| IGFOL-F (1019) | Grid current tracking error | The inverter cannot track the grid current correctly. | Restart the inverter; if it stays, contact Solis service. | Yes |
| PHASE-FAULT (101A) | Abnormal grid phase angle | The grid phase angle is abnormal. | Have the installer check the AC wiring and that the phases are 120 degrees apart, then restart. If it stays, contact Solis service. | Yes |
| OV-DC (1020) | DC (PV) overvoltage | The solar (DC) input voltage is too high. | Installer work: check that the string voltage is below the inverter's maximum input, then restart. If it stays, contact Solis service. | Yes |
| BoostFal (1020) | DC boost circuit fault | The DC boost circuit has a fault. | Restart the inverter; if it stays, contact Solis service. | Yes |
| OV-BUS (1021) | DC bus overvoltage | The internal DC bus voltage is too high. | Have the input voltage checked against the maximum, restart, and contact Solis service if it stays. | Yes |
| UNB-BUS (1022) | DC bus unbalanced | The internal DC bus and its half-voltage point do not match (bus unbalanced). | Restart the inverter; if it stays, contact Solis service. | Yes |
| UN-BUS (1023) | DC bus voltage too low | The internal DC bus voltage is too low. | Check whether the input voltage is too low and restart; if it stays, contact Solis service. | Yes |
| DC-INTF. (1027) | Abnormal DC input current | The DC input current is abnormal. | Have the installer check the DC wiring for wrong or damaged connections, then restart. If it stays, contact Solis service. | Yes |
| Reve-DC (1028) | DC reversely connected | A DC input is connected with reversed polarity. | Installer work: check the DC polarity and cable size and the grid standard setting, then restart. If it stays, contact Solis service. | Yes |
| PvMidIso / PVGndRun (1029) | PV mid-point low insulation / PV grounded during operation | The insulation at the PV mid-point is low, or a PV terminal is touching earth while running. | Installer work. In early morning or after rain it is usually moisture and clears by itself. Otherwise the installer measures each string's resistance to earth (it should be above about 20 kilo-ohm), checks neutral to earth and the software version, then contacts Solis service. | Yes |
| GRID-INTF. (1030) | Grid interference | The grid voltage waveform is distorted, often where several inverters share one line. | The installer may need grid filter settings or to repair equipment downstream, then restart. If it stays, contact Solis service. | Yes |
| INI-FAULT (1031) | DSP initializing fault | The control processor failed to start up properly. | Restart the inverter; if it stays, contact Solis service. | Yes |
| OV-TEM (1032) | Over temperature | The temperature near the power switches is above its limit (around 90 °C on single-phase and 115 °C on three-phase units). | Check the unit is not in direct sun and has the clearance the manual asks for, lower the room temperature, switch off and restart after fifteen minutes. If it stays, contact Solis service. | Usually not |
| PV ISO-PRO 01/02 (1033) | Low PV insulation protection | The insulation of the solar array to earth is too low. | Installer work. In early morning, late afternoon or rain it is often normal moisture. Otherwise the installer measures each string's resistance to earth (above about 20 kilo-ohm), checks neutral to earth, updates the software, then contacts Solis service. | Yes |
| ILeak-PRO 01-04 (1034) | Leakage current protection | Leakage current to earth is too high. Typical causes: damaged PV cable insulation, wrong cable size, a faulty transformer downstream, wrong rapid-shutdown wiring, wet buried AC cables or poor AC cable; in rain or early morning, ageing panels. | Installer work: connect the strings one at a time to find the faulty one. Solis support can sometimes fix it with a remote software update. | Yes |
| RelayChk-FAIL (1035) | Relay check failed | The grid relay failed its self-check. The source lists the code without a solution. | Restart; if it stays, contact Solis service, as for other internal faults. | Yes |
| Fan Alarm / Fan_H Alarm | Internal / external fan fault | The internal or external cooling fan has a fault. | Check the fan is not blocked; a replacement is installer work. | Yes |
| Surge Alarm | Grid surge recorded | A surge on the grid was recorded for service records; it does not stop the inverter. | No action needed. | Usually not |
| VgSpdFail | AC SPD fault | The AC surge protection device has a fault. | Restart the inverter; if it stays, contact Solis service. | Yes |
GoodWe ES Uniq hybrid error codes
GoodWe (ES Uniq hybrid; F-codes are shared across GoodWe residential inverters). Models: GW ES Uniq 8-12K with LX A/U batteries (manual read); on-grid DNS/MS/SDT and other hybrids (ET/EH) use the same F01-F163 numbering per this manual's 'all PV inverters' wording - verify per model
| Code | Meaning | Likely cause | What to do | Call installer? |
|---|---|---|---|---|
| F01 Grid Power Outage | No grid | There is no grid: a power cut, or the AC cable or AC switch is disconnected. | The code clears by itself when the grid returns. Check for load-shedding and that the AC switch and cable are connected. | Usually not |
| F02 Grid Overvoltage Protection | Grid voltage too high | The grid voltage is above the allowed range, or has stayed high longer than the high-voltage ride-through time. | If it happens now and then, the grid was briefly out of range and the inverter reconnects on its own. If it is frequent, check the grid voltage; if it is out of range, contact the DISCO. If it does not clear for a long time, check the AC breaker and output cable. | Usually not |
| F03 Grid Undervoltage Protection | Grid voltage too low | The grid voltage is below the allowed range, or has stayed low longer than the low-voltage ride-through time. | If it happens now and then, the grid was briefly out of range and the inverter reconnects on its own. If it is frequent, check the grid voltage; if it is out of range, contact the DISCO. If it does not clear for a long time, check the AC breaker and output cable. | Usually not |
| F04 Grid Rapid Overvoltage Protection | Sudden grid overvoltage | A sudden very high grid voltage, or a fault in the grid voltage measurement, tripped the inverter. | If it happens now and then, the grid was briefly out of range and the inverter reconnects on its own. If it is frequent, check the grid voltage; if it is out of range, contact the DISCO. If it does not clear for a long time, check the AC breaker and output cable. | Usually not |
| F05 10min Overvoltage | 10-minute average grid voltage too high | The grid voltage averaged over ten minutes is above the limit of the grid standard. | Check whether the grid voltage stays high for long periods; if it does, contact the DISCO. | Usually not |
| F06 Grid Overfrequency | Grid frequency too high | The grid frequency is above the local grid standard. | Occasional: the inverter reconnects by itself. Frequent: check the grid frequency and contact the DISCO. Protection limits change only with the DISCO's consent. | Usually not |
| F07 Grid Underfrequency | Grid frequency too low | The grid frequency is below the local grid standard. | Same as F06. | Usually not |
| F08 Grid Frequency Instability | Grid frequency changing too fast | The grid frequency is changing faster than the local grid standard allows. | Occasional: the inverter reconnects by itself. Frequent: contact the DISCO. | Usually not |
| F09 Anti-islanding Protection | Grid lost but voltage held by load; inverter stops grid connection | The grid has gone off but connected loads are holding up the voltage, so the inverter stops exporting as safety rules require. | Occasional: the inverter reconnects by itself. Frequent: contact the DISCO. | Usually not |
| F10 / F11 LVRT / HVRT fault | Grid voltage abnormal longer than ride-through time | The grid voltage stayed abnormal longer than the ride-through time. | Occasional: the inverter reconnects by itself. Frequent: check that grid voltage and frequency are in range and stable; if not, contact the DISCO. | Usually not |
| F12 / F13 / F14 / F15 GFCI Protection (30mA / 60mA / 150mA / slow change) | Leakage current to ground | Leakage current to earth tripped the inverter (the levels shown are the trip thresholds) because the insulation of the input side to earth dropped while running. | Occasional: a passing external fault, the inverter recovers by itself. Frequent or lasting: the installer should check the PV string-to-earth resistance. | Yes |
| F16 / F17 DCI Protection Level 1 / 2 | DC component in AC output too high | The DC part of the inverter's output current is above the allowed limit. | If an external fault caused it, the inverter recovers by itself. If it is frequent and cuts generation, contact the dealer or GoodWe service. | Yes |
| F18 Low Insulation Resistance | PV or battery insulation to ground too low | The PV string or battery port is shorted to earth, or long damp weather has lowered the insulation to earth. | Installer work: measure the string and battery port resistance to earth and find any short, and check the inverter's earth conductor. If the resistance is only low in rainy weather, the installer can adjust the insulation protection point in the app. | Yes |
| F19 Grounding Abnormal | Protective earth not connected | The inverter's protective earth is not connected, or a grounded PV string is used without an isolation transformer on the output. | Installer work: connect the protective earth properly; with a grounded PV string, fit an isolation transformer on the output. | Yes |
| F20 Hard Power Limit Protection | Abnormal load fluctuation | The load is fluctuating abnormally. | If an external cause, the inverter recovers by itself; if frequent, contact the dealer or GoodWe service. | Usually not |
| F21 Internal Comm Loss | Internal DSP communication timeout | An internal chip is not powered or has the wrong firmware, so internal communication timed out. | Switch off the AC output switch and the DC input switch, wait five minutes and switch them back on. If the fault stays, contact the dealer or GoodWe service. | Yes |
| F22-F27 Generator faults (waveform, abnormal connection, voltage low/high, frequency low/high) | Generator input out of range | The generator input is outside its limits. This shows all the time when no generator is connected. | With no generator connected, ignore it. With a generator it clears by itself once the generator runs normally; off-grid operation is not affected. | Usually not |
| F28 Parallel I/O Self-check Abnormal | Parallel communication cable / IO chip | A parallel communication cable is loose or the parallel I/O chip is damaged. | Installer work: secure the parallel communication cable; if the chip is damaged it must be replaced. | Yes |
| F29 Parallel Grid Line Reversed | Grid wires reversed between parallel units | Some parallel units have their grid wires reversed compared with the others. | Installer work: reconnect the grid wires correctly. | Yes |
| F30 AC HCT Check Abnormal | AC current sensor sampling abnormal | The AC current sensor reading is abnormal. | Switch off the AC output switch and the DC input switch, wait five minutes and switch them back on. If the fault stays, contact the dealer or GoodWe service. | Yes |
| F31 GFCI HCT Check Abnormal | Leakage current sensor sampling abnormal | The leakage-current sensor reading is abnormal. | Switch off the AC output switch and the DC input switch, wait five minutes and switch them back on. If the fault stays, contact the dealer or GoodWe service. | Yes |
| F32 Inverter Internal Failure | Internal fault detected | The inverter has detected an internal fault. | Switch off the AC output switch and the DC input switch, wait five minutes and switch them back on. If the fault stays, contact the dealer or GoodWe service. | Yes |
| F33 Flash R/W Abnormal | Flash memory read/write error | The internal flash memory changed unexpectedly or is worn out. | Update to the latest firmware; if it stays, contact the dealer or GoodWe service. | Yes |
| F34 AFCI Check Failure | Arc-fault self-check failed | The arc-fault module did not detect the test arc during its self-check. | Switch off the AC output switch and the DC input switch, wait five minutes and switch them back on. If the fault stays, contact the dealer or GoodWe service. | Yes |
| F35 Cabinet Overtemperature | Inverter too hot | The inverter is too hot: poor ventilation, a hot room, or the internal fan not working. | Improve ventilation and keep the room within the allowed temperature. If both are fine and it stays, contact the dealer or GoodWe service. | Usually not |
| F36 Bus Overvoltage | Internal DC bus voltage too high | The internal DC bus voltage is too high, from a high PV voltage or a measurement or transformer problem. | Switch off the AC output switch and the DC input switch, wait five minutes and switch them back on. If the fault stays, contact the dealer or GoodWe service. | Yes |
| F37 PV Input Overvoltage | PV string voltage above inverter maximum | Too many panels are connected in series, so the string's open-circuit voltage is above the inverter's maximum. | Installer work: re-design the string so its open-circuit voltage stays below the maximum; the alarm clears once it is correct. | Yes |
| F38 / F39 PV Continuous Hardware / Software Overcurrent | PV input overcurrent | The PV input current is too high, from a wrong module configuration or damaged hardware. | Switch off the AC output switch and the DC input switch, wait five minutes and switch them back on. If the fault stays, contact the dealer or GoodWe service. | Yes |
Sungrow SG RS on-grid error codes
Sungrow SG RS single-phase on-grid. Models: SG2.0RS-S / 2.5RS-S / 3.0RS-S / 3.0RS / 3.6RS / 4.0RS / 5.0RS / 6.0RS (manual says the code table covers 'all PV inverters' but only some apply per model)
| Code | Meaning | Likely cause | What to do | Call installer? |
|---|---|---|---|---|
| 002, 003, 014, 015 Grid Overvoltage | Grid voltage too high | The grid voltage is above the protection setting. The inverter normally reconnects once the grid is back to normal. | If it repeats, measure the grid voltage and contact the DISCO if it is above the setting, and have the protection settings checked in the app or display. Limits change only with the DISCO's consent. Contact Sungrow service if these are fine and the fault keeps coming. | Yes |
| 004, 005 Grid Undervoltage | Grid voltage too low | The grid voltage is below the protection setting. The inverter normally reconnects once the grid is back to normal. | If it repeats, measure the grid voltage and contact the DISCO, have the protection settings and the AC cable checked. Contact Sungrow service if these are fine and the fault keeps coming. | Yes |
| 008 Grid Overfrequency | Grid frequency too high | The grid frequency is above the protection setting. The inverter normally reconnects by itself. | If it repeats, measure the grid frequency and contact the DISCO if it is out of range, and have the protection settings checked. Contact Sungrow service if these are fine and the fault keeps coming. | Yes |
| 009 Grid Underfrequency | Grid frequency too low | The grid frequency is below the protection setting. The inverter normally reconnects by itself. | Same as 008. | Usually not |
| 010 Grid Power Outage | No grid | There is no grid. The inverter reconnects when the grid returns. | Check for load-shedding and that the AC breaker is on; the installer checks that the AC cable is tight and live and neutral are on the right terminals. Contact Sungrow service if these are fine and the fault keeps coming. | Yes |
| 012 Excess Leakage Current | Leakage current too high | Leakage current is too high, often from weak sunlight or a damp setting; the inverter usually reconnects when conditions improve. | If conditions are normal and it stays, the installer should check the insulation of the AC and DC cables. Contact Sungrow service if these are fine and the fault keeps coming. | Yes |
| 013 Grid Abnormal | Grid parameter out of range | A grid value is outside the set range. The inverter normally reconnects by itself. | Measure the grid and contact the DISCO if it is out of range. Contact Sungrow service if these are fine and the fault keeps coming. | Usually not |
| 017 Grid Voltage Imbalance | Phase voltages differ too much (3-phase) | On a three-phase supply, the phase voltages differ too much. The inverter normally reconnects by itself. | Measure the phase voltages and contact the DISCO if they differ a lot; the installer can adjust the imbalance setting. Contact Sungrow service if these are fine and the fault keeps coming. | Yes |
| 028, 029, 208, 212, 448-479 PV Reverse Connection Fault | PV string polarity reversed | A PV string is connected with reversed polarity (the code number shows which input or string). | Installer work: switch the DC isolator off once the string current is very low and correct the polarity. Contact Sungrow service if these are fine and the fault keeps coming. | Yes |
| 037 Excessively High Ambient Temperature | Inverter/module too hot | The inverter or its power module is too hot; it restarts once the temperature is normal. | Check that the room is not too hot, the unit is well ventilated and out of direct sun (shade it if not), and that the fan runs; a dead fan is replaced. Contact Sungrow service if these are fine and the fault keeps coming. | Yes |
| 039 Low System Insulation Resistance | PV/battery insulation to ground too low | The insulation of the system to earth is too low. | Installer work. Wait for the inverter to recover; if it repeats, check the insulation protection setting, measure the string and DC cable resistance to earth, re-check in dry weather if it only happens in rain, and check the battery cables. Contact Sungrow service if these are fine and the fault keeps coming. | Yes |
| 043 Excessively Low Ambient Temperature | Too cold to operate | The room is too cold for the inverter to run, so it stops. | It restarts when the temperature is back within its operating range. | Usually not |
| 075 Inverter Parallel Communication Alarm | Parallel communication cable problem | The parallel communication cable or its terminals have a problem. | Installer work: check and reconnect the communication cable. Contact Sungrow service if these are fine and the fault keeps coming. | Yes |
| 084 Reverse Connection Alarm of the Meter/CT | Energy meter or CT wired backwards | The energy meter or current sensor (CT) is wired wrongly or reversed. | Installer work: check the meter wiring and its input and output direction, and the rated power setting where an existing inverter is also connected. | Yes |
| 088 Electric Arc Fault | DC arc detected | An electric arc was detected on the DC side. | Installer work: switch the DC supply off and check for damaged DC cables and loose terminals or fuses, then switch back on and clear the fault in the app or display. Contact Sungrow service if these are fine and the fault keeps coming. | Yes |
| 106 Grounding Cable Fault | Earth/ground cable problem | The earth cable has a problem. | Installer work: check the AC cable connections and the insulation between earth and live. Contact Sungrow service if these are fine and the fault keeps coming. | Yes |
| 264-283 MPPT Reverse Connection | MPPT input polarity reversed | An MPPT input is connected with reversed polarity. | Installer work: switch the DC isolator off once the string current is very low and correct the polarity; otherwise contact Sungrow. | Yes |
| 323 Grid Confrontation | Output port connected to a live grid when it should not be | The inverter's output port is connected to a live grid where it should not be. | Installer work: disconnect the output from the grid. Contact Sungrow service if these are fine and the fault keeps coming. | Yes |
| 332-363 / 364-395 Boost Capacitor Overvoltage Alarm / Fault | Boost capacitor overvoltage | The boost capacitor voltage is too high. As an alarm (332-363) the inverter keeps running; as a fault (364-395) it stops. | Alarm: check the wiring and terminals and for anything foreign in the unit. Fault: switch off AC, DC and any battery switches, wait fifteen minutes, switch on AC and DC in turn and restart. Contact Sungrow service if these are fine and the fault keeps coming. | Yes |
| 514 Meter Communication Abnormal Alarm | Meter not communicating | The energy meter is not communicating. | Check and reconnect the meter's communication cable. Contact Sungrow service if these are fine and the fault keeps coming. | Yes |
| 532-547, 564-579 PV Reverse Connection Alarm | String polarity reversed (alarm level) | A PV string has reversed polarity (alarm level; the code shows which string). | Same as 028/029. | Yes |
| 548-563, 580-595 PV Abnormal Alarm | String producing abnormally (shading, loose wiring, fuse) | A PV string is producing less than expected: shading or dirt on its modules, loose wiring or a blown DC fuse. | You can check for shade and dirt on the panels; wiring and fuses are installer work. Contact Sungrow service if these are fine and the fault keeps coming. | Yes |
| System Fault (007, 011, 016, 019-025, 030-034, 036, 038, 040-042, 044-050, 052-058, 060-069, 085, 087, 092, 093, 100-105, 107-114, 116-124, 200-211, 248-255, 300-322, 324-328, 401-412, 600-603, 605, 608, 612, 616, 620, 622-624, 800, 802, 804, 807, 1096-1122) | Internal system fault | A general internal system fault. | Wait for the inverter to recover. If not, switch off AC, DC and any battery switches, wait fifteen minutes, switch on AC and DC in turn and restart. Contact Sungrow service if these are fine and the fault keeps coming. | Yes |
| System Alarm (059, 070-074, 076-083, 089, 216-218, 220-233, 432-434, 500-513, 515-518, 635-638, 900, 901, 910, 911, 996) | Non-blocking system alarm | A general system alarm; the inverter keeps running. | Check the related wiring and terminals and look for foreign objects or other problems around the unit, and correct them. Contact Sungrow service if these are fine and the fault keeps coming. | Yes |
Fronius Symo, Primo and GEN24 error codes
Fronius (Symo / Primo SnapINverter STATE codes; GEN24 1xxx codes). Models: Symo Hybrid (online manual read; Class 1-5 codes are shared with Symo/Primo/Galvo SnapINverters per Fronius numbering) and Primo GEN24 7.7/10.0 (GEN24 lists only 1030/1173/1191 in its manual)
| Code | Meaning | Likely cause | What to do | Call installer? |
|---|---|---|---|---|
| STATE 102 (also 103, 105, 106, 107, 108, 112) | AC (grid) voltage too high; class 1 codes = grid conditions outside permissible range | The grid voltage is too high (102). The other class 1 codes in this group cover grid voltage, frequency or islanding conditions outside the allowed range. | The inverter waits until the grid has been back in range for a while, then starts again. Check for grid problems; if the code keeps coming back, call the installer. | Usually not |
| STATE 301 | Overcurrent AC | The AC output current was too high. | Feed-in stops for a moment and the inverter starts again. If the code stays on permanently, a Fronius-trained technician is needed. | Yes |
| STATE 302 | Overcurrent DC or battery not detected | The DC current is too high, or the battery is not detected. | Same as 301. | Yes |
| STATE 303 / 304 | DC module overtemperature (PV) / AC module overtemperature | The DC (PV) or AC power module is too hot. | Clean the cooling air openings and heat sink. The inverter clears it by itself; if the code keeps coming back, call the installer. | Usually not |
| STATE 305 | No power being fed in, despite closed relays | The relays are closed but no power is being fed in. | The inverter clears it by itself; if the code keeps coming back, call the installer. | Usually not |
| STATE 306 (Power low) | Not enough PV power to feed in (normal at dawn/dusk) | There is not enough solar power to feed in and none is being drawn from the battery. At dawn and dusk this is routine, not a fault. | Wait for more sunlight. | Usually not |
| STATE 307 (DC low) | DC input voltage too low to feed in (normal at night) | The DC input voltage is too low to feed in; normal at night. | Wait for more sunlight. | Usually not |
| STATE 308 | Intermediate circuit voltage too high | The internal (intermediate circuit) voltage is too high. | The inverter clears it by itself; if the code keeps coming back, call the installer. | Usually not |
| STATE 401 | Unable to communicate with the power stage set | The inverter cannot communicate with its power stage. | It retries by itself and resumes feeding in when it can. If the code stays permanently, a Fronius-trained technician is needed. | Yes |
| STATE 406 / 407 / 408 | DC module temperature sensor faulty (PV) / AC module temperature sensor faulty / DC component measured in the grid too high | A temperature sensor on the DC or AC module is faulty (406, 407), or the DC part measured in the grid is too high (408). | If the code keeps coming back, call the installer. | Yes |
| STATE 412 | Fixed voltage mode selected instead of MPP voltage mode | The inverter is set to a fixed input voltage instead of tracking the best (MPP) voltage, and the fixed value is too low or too high. | A setting the installer has to correct. | Yes |
| STATE 416 | No communication between power stage set and control system | The power stage and the control system cannot communicate. | Same as 401. | Yes |
| STATE 457 | Grid relay sticking or neutral conductor ground voltage too high | A grid relay is sticking, or the neutral-to-earth voltage is too high; the inverter has stopped feeding in. | Installer work: check the earthing so the neutral-to-earth voltage stays below 30 V. | Yes |
| STATE 459 / 460 / 461 | Error recording the measuring signal for the insulation test / DSP reference voltage out of tolerance / DSP data memory error | An internal check failed: the insulation-test measurement, a processor reference voltage or the processor's data memory. The inverter is not feeding in. | If the code stays permanently, a service technician is needed. | Yes |
| STATE 502 | Insulation fault on solar modules or on the battery | There is an insulation fault on the solar modules or the battery. | If the code keeps coming back, call the installer. | Yes |
| STATE 509 | No energy fed into the grid in the past 24 hours | No energy has been fed into the grid in the past 24 hours. | Acknowledge the code and check that feed-in is possible: DC switch on, panels not shaded, dirty or covered. If all is fine, call the installer. | Usually not |
| STATE 522 | DC low (PV), no PV voltage available | There is no PV voltage (DC low). At night, or in standby, this is normal. | No action at night. In the day, check the DC switch; if it is on, call the installer. | Usually not |
| STATE 558 | Functional incompatibility between PC boards | Some circuit boards in the inverter are not compatible with each other. | The inverter firmware needs updating by the installer or Fronius service. | Yes |
| STATE 567 | Power derating caused by overvoltage | Output power is being reduced because the grid voltage is very high. | It clears by itself once the grid voltage is back in range; if it keeps coming back, call the installer. | Usually not |
| 1030 WSD Open (GEN24) | Wired shutdown chain open | The wired shutdown (WSD) chain is open: a connected device such as a surge protector broke the signal line, or the factory bypass was removed without fitting a trigger device. | Installer work: if the surge protector tripped, an authorised specialist must repair the inverter; otherwise refit the bypass or a trigger device, or set the WSD switch to position 1 (primary device). | Yes |
| 1173 ArcContinuousFault (GEN24) | Repeated DC arc detected; max auto-reconnects reached | An electric arc was detected on the PV system and the inverter has used up its automatic restarts for the day. | Do not just clear it: the whole affected PV system must first be checked for damage, and damaged parts repaired by qualified specialists. Only then is the status confirmed (sensor held three seconds, or in the event log). | Yes |
| 1191 AfciDataTransfer (GEN24) | Arc identified (info) | An electric arc was detected on the PV system (information only). | No action needed by itself; if it repeats it becomes 1173. | Usually not |
Inverex Nitrox on-grid error codes
Inverex Nitrox (on-grid, three-phase). Models: NITROX-12KW, 15KW, 20KW, 25KW and the -3Ph-5G versions (the manual lists all of them)
| Code | Meaning | Likely cause | What to do | Call installer? |
|---|---|---|---|---|
| F01 | DC input polarity reverse fault | The manual gives only the code's name (table 10.1), no cause. | Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F02 | DC insulation impedance permanent fault | The manual gives only the code's name (table 10.1), no cause. | Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F03 | DC leakage current fault | The manual gives only the code's name (table 10.1), no cause. | Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F04 | Ground fault GFDI | The manual gives only the code's name (table 10.1), no cause. | Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F05 | Read the memory error | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F06 | Write the memory error | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F07 | GFDI blown fuse | The manual gives only the code's name (table 10.1), no cause. | Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F08 | GFDI grounding touch failure | The manual gives only the code's name (table 10.1), no cause. | Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F09 | IGBT damaged by excessive drop voltage | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F10 | Auxiliary switch power supply failure | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F11 | AC main contactor errors | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F12 | AC auxiliary contactor errors | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F14 | DC firmware over current | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F15 | AC firmware over current | Surge loads on the grid. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F16 | GFCI (RCD) AC leakage current fault | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If it trips again, do not keep resetting it: earth leakage can mean a shock risk, so call the installer. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F17 | Three phase current, over-current fault | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F18 | AC over current fault of hardware | Surge loads on the grid. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F19 | All hardware failure synthesis | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F20 | DC over current fault of the hardware | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F21 | DC leakage flow fault | The manual gives only the code's name (table 10.1), no cause. | Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F22 | Crash stop (if there is a stop button) | The manual gives only the code's name (table 10.1), no cause. | Release the emergency stop button if one is fitted, then restart the inverter. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Usually not |
| F23 | AC leakage current is transient over current | Ground error, or PV+ or PV- shorted to ground. | Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F24 | DC insulation impedance failure | PV+ or PV- to ground resistance is too low. | Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F25 | DC reverse irrigation failure | The manual gives only the code's name (table 10.1), no cause. | Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F26 | The DC busbar is unbalanced | Loss of one phase, a poor connection, or inverter hardware damage. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F27 | DC end insulation error | The manual gives only the code's name (table 10.1), no cause. | Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F28 | Inverter 1 DC high fault | The manual gives only the code's name (table 10.1), no cause. | Do not open the DC (solar) side yourself: a high DC voltage can come from the panel string, and PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F29 | AC load switch failure | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F30 | AC main contactor failure | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F31 | AC secondary contactor failure | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F32 | Inverter 2 DC high fault | The manual gives only the code's name (table 10.1), no cause. | Do not open the DC (solar) side yourself: a high DC voltage can come from the panel string, and PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F33 | AC over current | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F34 | AC current over load | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F35 | No AC grid | Grid failure. | Usually clears by itself when the grid voltage and frequency return to normal (common during loadshedding and low voltage). If it shows every day, ask the installer to check the grid protection settings and the AC cable. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Usually not |
| F36 | AC grid phase error | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F37 | AC three-phase voltage imbalance failure | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F38 | AC three-phase current imbalance failure | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F39 | AC over current | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F40 | DC over current | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F41 | AC line W,U over voltage | Grid voltage or frequency outside the inverter's normal working range. | Usually clears by itself when the grid voltage and frequency return to normal (common during loadshedding and low voltage). If it shows every day, ask the installer to check the grid protection settings and the AC cable. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Usually not |
| F42 | AC line W,U low voltage | Grid voltage or frequency outside the inverter's normal working range. | Usually clears by itself when the grid voltage and frequency return to normal (common during loadshedding and low voltage). If it shows every day, ask the installer to check the grid protection settings and the AC cable. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Usually not |
| F43 | AC line V,W over voltage | Grid voltage or frequency outside the inverter's normal working range. | Usually clears by itself when the grid voltage and frequency return to normal (common during loadshedding and low voltage). If it shows every day, ask the installer to check the grid protection settings and the AC cable. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Usually not |
| F44 | AC line V,W low voltage | Grid voltage or frequency outside the inverter's normal working range. | Usually clears by itself when the grid voltage and frequency return to normal (common during loadshedding and low voltage). If it shows every day, ask the installer to check the grid protection settings and the AC cable. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Usually not |
| F45 | AC line U,V over voltage | Grid voltage or frequency outside the inverter's normal working range. | Usually clears by itself when the grid voltage and frequency return to normal (common during loadshedding and low voltage). If it shows every day, ask the installer to check the grid protection settings and the AC cable. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Usually not |
| F46 | AC line U,V low voltage | Grid voltage or frequency outside the inverter's normal working range. | Usually clears by itself when the grid voltage and frequency return to normal (common during loadshedding and low voltage). If it shows every day, ask the installer to check the grid protection settings and the AC cable. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Usually not |
| F47 | AC over frequency | Grid voltage or frequency outside the inverter's normal working range. | Usually clears by itself when the grid voltage and frequency return to normal (common during loadshedding and low voltage). If it shows every day, ask the installer to check the grid protection settings and the AC cable. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Usually not |
| F48 | AC lower frequency | Grid voltage or frequency outside the inverter's normal working range. | Usually clears by itself when the grid voltage and frequency return to normal (common during loadshedding and low voltage). If it shows every day, ask the installer to check the grid protection settings and the AC cable. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Usually not |
| F49 | U phase grid current DC over current | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F50 | V phase grid current DC over current | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F51 | W phase grid current DC over current | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F52 | AC inductor A phase current DC current high | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F53 | AC inductor B phase current DC current high | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F54 | AC inductor C phase current DC current high | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F55 | DC busbar voltage is too high | Solar (PV) over voltage. | Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F56 | DC busbar voltage is too low | Solar (PV) under voltage. | Do not open the DC (solar) side yourself: PV strings are live whenever there is daylight, even with the DC breaker off. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F57 | AC reverse irrigation | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F58 | AC grid U over current | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F59 | AC grid V over current | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F60 | AC grid W over current | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F61 | Reactor A phase over current | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F62 | Reactor B phase over current | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F63 | Reactor C phase over current | The manual gives only the code's name (table 10.1), no cause. | Switch the inverter off and on once. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Yes |
| F64 | IGBT heat sink high temperature | The manual gives only the code's name (table 10.1), no cause. | Check that the inverter's air vents are not blocked and that it is out of direct sun. If the fault stays after a reset, contact the Inverex distributor with the serial number, installation date, the LCD code and the LED status. | Usually not |
Voltronic Axpert error codes
Voltronic Power Axpert (base design of many Pakistani rebrands). Models: Axpert VM III 1.5/3/5 kW (manual read). Other Axpert families (VM IV, MKS IV, MAX, MAX II, King) use the same 01-09 / 51-59 numbering with model-specific additions (MAX II adds 11 PV over voltage, 12 DC/DC over current, 13 battery discharge over current, per voltronicpower.com manual listing - not read). Pakistani brands sold as 'Axpert'-type units (e.g. Inverex Axpert, Ziewnic Axpert) are widely reported to be Voltronic OEM units, but no Inverex/Knox manual was fetched to confirm their code tables.
| Code | Meaning | Likely cause | What to do | Call installer? |
|---|---|---|---|---|
| Fault 01 | Fan is locked / fan fault | The cooling fan has failed. | Clean dust from the fan; if it does not turn, the installer replaces it. | Yes |
| Fault 02 | Over temperature | A part inside the inverter is too hot (above about 100 to 120 °C). | Make sure air can flow around the unit and the room is not too hot. | Usually not |
| Fault 03 | Battery voltage is too high | The battery is over-charged or its voltage is too high. | Have the installer check that the battery type, number of batteries and charge settings suit the inverter; otherwise the unit needs the service centre. | Yes |
| Fault 04 | Battery voltage is too low | The battery voltage is too low (below about 1.91 V per cell at start-up). | Recharge the battery; if it will not hold charge, it needs replacing. | Usually not |
| Fault 05 | Output short circuited (or converter over-temperature) | The output is short-circuited, or an internal part has overheated. | Switch the loads off and look for a faulty appliance or wiring fault; if it stays, call the installer. | Yes |
| Fault 06 / 58 | Output voltage too high / too low | The output voltage is outside its normal band (below about 190 V or above about 260 V). | Reduce the load. If it repeats, the unit needs the service centre. | Yes |
| Fault 07 | Overload time out | The load has been above about 110% of the rating for too long. A PV voltage above the specification also reduces output power and can cause this. | Switch some appliances off; if the PV voltage is too high, the installer reduces the number of panels in series. | Usually not |
| Fault 08 / 09 / 53 / 57 | Bus voltage too high / bus soft start failed / inverter soft start failed / current sensor failed | An internal component has failed. | The unit needs the service centre. | Yes |
| Fault 51 | Over current or surge | An over-current or surge was detected. | Restart the unit; if the code comes back, it needs the service centre. | Yes |
| Fault 52 | Bus voltage is too low | The internal DC bus voltage is too low. | Restart the unit; if the code comes back, it needs the service centre. | Yes |
| Fault 55 | Over DC voltage in AC output / output voltage unbalanced | The output voltage is unbalanced. | Restart the unit; if the code comes back, it needs the service centre. | Yes |
| Fault 59 | PV voltage is over limitation | The PV input voltage is above the specification. | Installer work: reduce the number of panels in series. | Yes |
| Warning 01 | Fan is locked when inverter is on (beep three times every second) | Fan warning. | Check that the fan turns freely; if it stays, call the installer. | Usually not |
| Warning 02 | Over temperature (no beep) | Over-temperature warning. | Reduce the load and improve ventilation. | Usually not |
| Warning 03 | Battery is over-charged (beep once every second) | Battery over-charge warning. | Have the installer check the charger and battery settings. | Yes |
| Warning 04 | Low battery (beep once every second) | Low battery warning. | Recharge the battery and reduce the load. | Usually not |
| Warning 07 | Overload (beep once every 0.5 second) | Overload warning. | Switch some loads off. | Usually not |
| Warning 10 | Output power derating (beep twice every 3 seconds) | Output power is being reduced (derating). | Reduce the load; see Fault 07 on derating from a high PV voltage. | Usually not |
| Warning 15 | PV energy is low (beep twice every 3 seconds) | Solar power is low. | Normal in low sun; no action needed. | Usually not |
| Warning 16 | High AC input (>280VAC) during BUS soft start | The grid (utility) voltage is out of range. | Wait for the grid voltage to settle; if it is frequent, the installer checks the input voltage. | Usually not |
| Warning 32 | Communication failure between inverter and remote display panel | The display panel is not communicating. | Check the display cable; if it stays, call the installer. | Usually not |
| Warning (battery icon) | Battery is not connected / Battery equalization | The battery is disconnected; the relay may click on and off repeatedly. | Check that the battery cables are connected tightly (switch off first). | Usually not |
Common mistakes
- Restarting again and again. A code that returns after one restart has a cause; repeated restarts can damage the inverter.
- Ignoring grid over-voltage codes. If the inverter trips every afternoon, log the voltage it shows and report it to the DISCO; the inverter is doing its job.
- Reading another brand's table as your own. Fault numbers differ between platforms; use your brand's table or your printed manual.
- Opening DC connectors with the sun up. PV strings are live whenever there is light; only an installer with the right tools should touch them.
Safety: PV strings and batteries carry dangerous DC voltage and current. Switch off AC and DC isolators in the order your manual gives before touching anything, and leave any work inside the inverter or on the DC side to a licensed electrician or your installer.
Frequently asked questions
What does a solar inverter error code mean?
It is the inverter reporting which protection tripped: grid voltage or frequency out of range, PV voltage too high, battery too low or too high, over temperature, overload, insulation fault and so on. Pick your brand above and type the code to read the manufacturer's meaning and remedy.
My Inverex error code is not in the list. What now?
If you have a Nitrox on-grid inverter, pick Inverex Nitrox in the brand list: every F code from its manual is there. Manuals for the Inverex Veyron and Aerox hybrids were not available with Inverex's name on them when we checked, so those codes are not listed yet. Most of these hybrids follow the Voltronic Axpert table; compare the number there and with your printed manual, and send us the manual's fault table through the contact page so we can add it.
Why does my on-grid inverter stop every afternoon with a grid voltage code?
The street voltage rises when many solar systems export at once and the inverter must disconnect above its limit. Note the voltage shown on the display and report it to your DISCO; an installer can also check the AC cable size and connections, which add to the voltage the inverter sees.
Can I clear an error code by restarting the inverter?
Often, for a one-off trip. Switch off AC then DC, wait about a minute, switch on in the order your manual gives. If the code returns, stop restarting and call the installer.
Which codes mean the battery is the problem?
Battery voltage high or low, battery over-current, battery over-temperature and battery communication (BMS) errors. Check the battery breaker and connections are tight and the battery is not flat; lithium batteries also need the communication cable in place.
Where do these tables come from?
From the manufacturers' own manuals and support pages, listed under Sources with a link for each brand and the date we last checked them. Each row is our own plain-English summary of the manual's entry, not a copy of it.
Sources
- Wattlyst methodology and editorial policy
- Growatt SPF (off-grid / hybrid 'ES' series): Growatt SPF 6000 ES PLUS User Manual v1.0
- Growatt MIN / MOD on-grid (TL-X family): Growatt MIN 2500-6000TL-X User Manual GR-UM-155-A-04
- Huawei SUN2000 (L1 single-phase residential): SUN2000-(2KTL-6KTL)-L1 User Manual Issue 10 (2022-10-27)
- Solis (Ginlong) on-grid and hybrid: Solis North America support article 'Solis Inverter Alarm Codes (Complete List)'
- GoodWe (ES Uniq hybrid; F-codes are shared across GoodWe residential inverters): GoodWe Residential Smart Inverter Solutions User Manual (ES Uniq 8-12K
- Sungrow SG RS single-phase on-grid: Sungrow SG2.0RS-S...SG6.0RS User Manual SG2.0-6.0RS-UEN-Ver21-202312
- Fronius (Symo / Primo SnapINverter STATE codes; GEN24 1xxx codes): Fronius Symo Hybrid Operating Instructions (online manual 42
- Inverex Nitrox (on-grid, three-phase): Inverex NITROX-12KW User Manual
- Voltronic Power Axpert (base design of many Pakistani rebrands): Voltronic Axpert VM III User Manual v1.8
Last updated: