Watts to Amps Calculator for DC, Single-Phase and Three-Phase
1,500 watts is 8.15 amps on a 230 V single-phase supply at a power factor of 0.8, or 6.52 A for a heater with a power factor of one. Amps = watts ÷ (volts × power factor); for DC the power factor is one, and for three-phase the volts are multiplied by the square root of three.
How this result was calculated
1,500 W ÷ (1 × 230 V × 0.8 power factor) = 8.15 A. The first factor is one for DC and single-phase and √3 for three-phase, where the volts are the line-to-line voltage and the result is the current in each line. On DC the power factor is always one, so amps are simply watts ÷ volts.
Key facts
- Amps = watts ÷ (volts × power factor). On a 230 V single-phase supply, 1,500 W at a power factor of 0.8 draws 8.15 A.
- Watts alone do not give amps: the same 1,000 W draws 83.33 A from a 12 V battery but only 4.35 A at 230 V mains with a power factor of one.
- At 120 V (US and Canada) a 1,500 W heater draws 12.5 A, close to twice the 6.52 A the same heater draws on a 230 V supply.
- On three-phase 400 V, 10,000 W at a power factor of 0.8 draws 18.04 A in each line wire.
Formula
DC: I = P ÷ V; single-phase AC: I = P ÷ (V × PF); three-phase AC: I = P ÷ (√3 × V × PF)
- I = current in amps (A)
- P = real power in watts (W); for kW multiply by 1,000
- V = voltage: the battery voltage for DC, phase-to-neutral for single-phase, line-to-line for three-phase
- PF = power factor between 0 and 1 (1 for heating loads)
- √3 ≈ 1.732, three-phase only
What is 1,500 W in amps?
On a 230 V home supply, 1,500 W is 6.52 A for a heater, kettle or iron (power factor one) and 8.15 A for a motor or AC at a power factor of 0.8. The watts are the same; the motor draws more current because part of it flows back and forth without doing work.
On a 120 V US supply the same heater draws 12.5 A, close to twice as much current, so always enter the voltage of the supply the load actually runs on.
Is 1,000 watts one amp? How many watts per amp?
No. A watt is power, an amp is current, and the voltage links them. 1,000 W is 83.33 A from a 12 V battery but 4.35 A from 230 V mains. The higher the voltage, the fewer amps for the same watts.
Each amp carries as many watts as the voltage times the power factor: on 230 V mains with a power factor of one, one amp is 230 W. The amps to watts calculator does that direction.
Watts, amps and volts: how they relate
Power is voltage times current. On DC that is the whole story: watts = volts × amps. On AC the current and voltage are slightly out of step in motors, compressors and electronics, so a power factor below one is added: watts = volts × amps × power factor.
Three-phase supplies use three live wires. The power is shared between them, so the formula uses the square root of three and the line-to-line voltage (400 V in Pakistan), and the result is the current in each line.
DC watts to amps: batteries, solar and cars
Choose DC and enter the battery voltage. A 1,000 W load on a 12 V battery draws 83.33 A, which is why low-voltage inverters need thick cables. On a battery inverter, add the inverter's losses to the watts first; the 12V watts to amps calculator does this for you.
Worked examples
What is 1,500 W in amps on a 230 V supply?
1,500 W ÷ (230 V × 1) = 6.52 A for a heater or kettle. A motor of the same watts at a power factor below one draws more.
1,000 W from a 12 V battery (DC)
1,000 W ÷ 12 V = 83.33 A. DC has no power factor, so this is the current the battery and its cable must carry, before inverter losses.
10,000 W on three-phase 400 V
10,000 W ÷ (√3 × 400 V × 0.8) = 18.04 A in each line. The voltage box was left blank, so the calculator used the standard three-phase line-to-line voltage.
1,500 W heater at 120 V (US and Canada)
1,500 W ÷ (120 V × 1) = 12.5 A. A lower voltage means more amps for the same watts.
How many amps is 1,000 watts at 230 V?
1,000 W ÷ (230 V × 1) = 4.35 A for a resistive load such as an iron or water heater.
Watts to amps chart: common loads on DC batteries, single-phase mains and three-phase supplies
| Power | Voltage | Power factor | Current |
|---|---|---|---|
| 100 W | 12 V | 1 | 8.33 A |
| 1,000 W | 48 V | 1 | 20.83 A |
| 500 W | 230 V | 1 | 2.17 A |
| 2,000 W | 230 V | 1 | 8.7 A |
| 2,000 W | 230 V | 0.8 | 10.87 A |
| 3,000 W | 230 V | 1 | 13.04 A |
| 2,000 W | 120 V | 1 | 16.67 A |
| 20,000 W | 400 V | 0.8 | 36.08 A |
Common mistakes
- Dividing watts by volts for an AC, fridge or water motor. Their power factor is below one, so the real current is higher; use about 0.8 unless the label says otherwise.
- Using 230 V in the three-phase formula. Three-phase needs the line-to-line voltage (400 V) together with the square root of three.
- Forgetting that DC current is large at low voltage. A load that draws a few amps from the mains can draw tens of amps from a battery, and the cable must be sized for that.
- Treating the calculated amps as the breaker or wire size. Cables and breakers need a margin above the running current; the breaker size calculator adds it.
Safety: The current from this page is a starting point for choosing cable and breakers, not the final choice. Use the wire size and breaker size calculators for the margins and voltage drop, and have a licensed electrician connect any new circuit.
Frequently asked questions
How many amps is 1,000 watts?
4.35 A on a 230 V single-phase supply with a power factor of one. From a 12 V battery the same 1,000 W draws 83.33 A, because current depends on the voltage.
What is 1,500 W in amps?
6.52 A at 230 V for a heating load, and 8.15 A at a power factor of 0.8 for a motor or mixed load.
How many amps does a 1,500 W heater draw at 120 V?
12.5 A at 120 V, against 6.52 A on a 230 V supply. Roughly halving the voltage roughly doubles the current, which is why US heaters need heavier cable.
What is the watts to amps formula?
Amps = watts ÷ volts for DC; amps = watts ÷ (volts × power factor) for single-phase AC; amps = watts ÷ (√3 × line-to-line volts × power factor) for three-phase.
Is 1,000 watts one amp?
No. Watts measure power and amps measure current. 1,000 W is 4.35 A on 230 V mains and 83.33 A from a 12 V battery.
How many watts per amp?
Watts per amp equals the voltage times the power factor. On 230 V mains with a power factor of one, each amp carries 230 W; on a 12 V battery each amp carries only 12 W.
How do I convert watts to amps on three-phase?
Divide the watts by √3 × the line-to-line voltage × the power factor. 10,000 W at 400 V and a power factor of 0.8 is 18.04 A per line. The 3 phase amps calculator also handles kW and kVA ratings.
Sources